Troubleshooting
Service manual
24
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
3.3.7 80-00 – Inlet water thermistor abnormality
Trigger
Effect
Reset
Inlet water thermistor
input is out of range.
Unit will stop operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the inlet water thermistor. See
Possible cause:
Faulty inlet water thermistor.
2
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.8 81-00 – Outlet water thermistor abnormality
Trigger
Effect
Reset
Outlet water thermistor
input is out of range.
Unit will stop operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outlet water after backup heater thermistor. See
Possible cause:
Faulty outlet water after backup heater thermistor.
2
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.9 81-01 – Mixed water thermistor abnormality
Trigger
Effect
Reset
Outlet water thermistor
bizone input is out of
range.
Unit will not stop
operating.
Automatic reset.