5.3 Water circuit
5.3.1 Checking procedures
To check for an external pump
1
Inspect the installation outside the unit and check for the presence of an
external pump. This may have an impact on the water flow inside the unit.
An external pump was found in the
installation?
Action
Yes
Remove the external pump from the
installation, see
269].
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To check the water pressure
1
Turn ON the power of the unit.
INFORMATION
Make sure that the water pressure sensor is functioning correctly.
2
Read the water pressure on the home screen of the user interface.
Result:
The pressure MUST be 1~2 bar.
Is the water pressure correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Add or remove water from the water
circuit until the pressure is correct, see
To check the water flow
1
Turn ON the power using the respective circuit breaker.
2
Ensure the heat/cool emitters are open.
3
Activate air purge operation of the space heating/cooling circuit via the user
interface and select pump speed "High", see installer reference guide for
correct procedure.