5
|
Third party components
Service manual
266
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
INFORMATION
Make sure that the water flow sensor is functioning correctly.
4
Navigate to the information menu on the user interface, see installer
reference guide for correct procedure.
5
Read the water flow in the information menu on the user interface.
Result:
The water flow MUST be at least:
If operation is…
Then the minimum required flow rate
is…
Cooling
10 l/min
Heating
6 l/min
BUH operation
12 l/min
Heating defrost
12 l/min
DHW
25 l/min
Is the water flow correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Continue with the next step.
6
Is the water pressure correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Add or remove water from the water
circuit until the pressure is correct, see
269].
To check if the water circuit stop valves are open
1
The stop valves are located outside the unit. Check that all valves are in open
position (in line with the piping).
All valves are open?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Open the specific valve(s) of the water
circuit, see
To check for an external heat source
1
Inspect the installation outside the unit and check for the presence of an
external heat source. This may have an impact on the water temperature
inside the unit.