4
|
Components
Service manual
142
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
4.5 Booster heater
4.5.1 Checking procedures
To perform a resistance check of the booster heater
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Check that the booster heater thermal protector functions correctly.
Reset if it has tripped. See
"4.6 Booster heater thermal protector"
147].
1
Remove the required plate work, see
202].
a
a
Booster heater contactor K3M
2
Measure the booster heater resistance between K3M/1 and K3M/3.
Result:
The measured resistance MUST be approximately 18 Ω.
INFORMATION
See the
281] for more detailed information.
INFORMATION
Make sure that the wiring between the booster heater contactor and the booster
heater is properly connected and NOT damaged (check continuity), see
281].
Is the measured booster heater
resistance correct?
Action
Yes
heater and continue with the next
procedure.
No
Replace the booster heater, see
146].
draft – 31/05/2022 15:53
Summary of Contents for EBLA04E V Series
Page 322: ...14 14...
Page 323: ......