6
|
Maintenance
Service manual
276
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
4
Clean the filter with water and a soft brush.
a
Filter
5
When cleaned, reinstall the filter in the shut‑off valve.
NOTICE
Handle the water filter with care. Do NOT use excessive force when you reinsert the
water filter so as NOT to damage the water filter mesh.
6
Screw the bottom cap back on.
7
Open the shut‑off valve.
8
Make sure that the air purge valves are in the open position.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
6.3 To check the pipe heaters
The unit contains several pipe heaters to avoid freezing of the water circuit. Yearly
check the correct functioning of these pipe heaters and repair as needed.
Below is an overview of the different pipe heaters and technical data. Also check
the
draft – 31/05/2022 15:53