
Configuration Mode (ConF)
86
Code
Nam e / De s cription
Adjus tment range Factory s e tting
CCFG
[Customized macro]
*
Read-only parameter, only visible if at least one macro configuration parameter has been modified.
nO
[No]
(nO)
: No
YES
[Ye s ]
(YES)
: Yes
bFr
[Standard mot. freq]
[50Hz IEC]
(50)
50
This parameter modifies the presets of the follow ing parameters:
[Rate d m otor volt.]
(UnS)
below ,
[High s pe e d]
(HSP)
page
87
,
[Freq. thres hold]
(Ftd)
page
102
,
[Rate d motor freq.]
(FrS)
and
[Max freque nc y ]
(tFr)
.
[50Hz IEC]
(50)
: Drive 50 Hz
[60Hz NEM A]
( 0)
: Drive 60 Hz
0
IPL
[Input phase loss]
Yes or No, according to drive
rating
*
This parameter is only accessible in this menu on 3-phase drives.
If one phase disappears, the drive sw itches to fault mode
[Input phas e loss]
(PHF)
, but if 2 or 3 phases disappear, the drive
continues to operate until it trips on an undervoltage detected fault (the drive trips in
[Input phase los s]
(PHF)
if there is an
input phase loss and if this leads to performance decrease).
See
[Input phas e los s ]
(IPL)
page
256
.
[Ignore]
(nO)
: Detected fault ignored, to be used w hen the drive is supplied via a single-phase supply or by the DC bus
[Fre ewheel]
(YES)
: With freewheel stop
nO
YES
nPr
*
[Rated motor power]
According to drive rating
Rated motor pow er given on the nameplate, in kW if
[Standard m ot. fre q]
(bFr)
is set to
[50Hz IEC]
(50)
, in HP if
[Standard m ot. fre q]
(bFr)
is set to
[60Hz NEM A]
( 0)
.
See
[Rate d m otor pow e r]
(nPr)
page
107
.
UnS
*
[Rated motor volt.]
100 to 480 V
According to drive rating
Rated motor voltage given on the nameplate.
ER24-…K/B: 100 to 240 V – ER24-…/4K/B: 200 to 480 V.
See
[Rate d m otor volt.]
(UnS)
page
107
.
nCr
*
[Rated mot. current]
0.25 to 1.5 In (1)
According to drive rating and
[Standa rd mot. freq]
(bFr)
Rated motor current given on the nameplate.
See
[Rate d m ot. current]
(nCr)
page
107
.
FrS
*
[Rated motor freq.]
10 to 800 Hz
50 Hz
Rated motor frequency given on the nameplate.
The factory setting is 50 Hz, or preset to 60 Hz if
[Standard m ot. freq]
(bFr)
is set to 60 Hz.
This parameter is not visible if
[Motor control type]
(Ctt)
page
105
is set to
[Sync . mot.]
(SYn)
.
See
[Rate d m otor fre q.]
(FrS)
page
107
.
nSP
*
[Rated motor speed]
0 to 65,535 rpm
According to drive rating
Rated motor speed given on the nameplate.
This parameter is not visible if
[Motor control type]
(Ctt)
page
105
is set to
[Sync . mot.]
(SYn)
.
See
[Rate d m otor s pe ed]
(nSP)
page
107
.
0 to 9,999 rpm then 10.00 to 60.00 krpm on the integrated display terminal.
If, rather than the rated speed, the nameplate indicates the synchronous speed and the slip in Hz or as a %, calculate the rated
speed as follow s:
100 - slip as a %
Nominal speed = Synchronous speed x
100
or
50 - slip in Hz
Nominal speed = Synchronous speed x
(50 Hz motors)
50
or
Nominal speed = Synchronous speed x
60 - slip in Hz
(60 Hz motors)
60
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > SIM-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...