Configuration Mode (ConF)
272
Process overload detected fault
A proces s overload is detected when the next event occurs and rem ains pending for a m inim um tim e
[Ovld Time Detect.]
(tOL)
, which is configurable:
•
The drive is in current lim itation m ode.
•
The m otor is in s teady s tate and the current is above the s et overload thres hold
[Ovld Detection Thr.]
(LOC)
.
The m otor is in s teady s tate when the offs et between the frequency reference and motor frequency falls below
the configurable thres hold
[Hysteresis Freq. Att.]
(Srb)
.
A relay or a logic output can be as s igned to the s ignaling of this detected fault in the
[INPUTS / OUTPUTS CFG]
(I_O-)
m enu.
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FLt-
[FAULT MANAGEMENT]
(continued)
OLd-
[PROCESS OVERLOAD]
tOL
[Ovld Time Detect.]
0 to 100 s
0 s
Overload detection time delay.
A value of 0 deactivates the function and makes the other parameters inaccessible.
LOC
*
(1)
[Ovld Detection Thr.]
70 to 150%
110%
Overload detection threshold, as a % of the rated motor current
[Rate d m ot. current]
(nCr)
page
86
. This value must be less
than the limit current in order for the function to w ork.
Srb
*
(1)
[Hysteresis Freq.Att.]
0 to 599 Hz
0.3 Hz
Maximum deviation betw een the frequency reference and the motor frequency, which defines steady state operation.
OdL
*
nO
YES
rMP
FSt
[Ovld.Proces.Mngmt]
[Fre e w heel]
(YES)
Behavior on sw itching to overload detection.
[Ignore ]
(nO)
: Detected fault ignored
[Fre e w heel]
(YES)
: Freew heel stop
[Ram p s top]
(rMP)
: Stop on ramp
[Fas t s top]
(FSt)
: Fast stop
FtO
*
(1)
[Overload T.B.Rest.]
0 to 6 min
0 min
This parameter cannot be accessed if
[Ovld.Proces.Mngmt]
(OdL)
is set to
[Ignore]
(nO)
.
Minimum time permitted betw een an overload being detected and any automatic restart.
In order to allow an automatic restart, the value of
[Max. resta rt time]
(tAr)
page
252
must exceed this paramet er by at least
one minute.
FLt-
[FAULT MANAGEMENT]
(continued)
LFF-
[FALLBACK SPEED]
LFF
[Fallback speed]
0 to 599 Hz
0 Hz
Selection of the fallback speed.
FLt-
[FAULT MANAGEMENT]
(continued)
FSt-
[RAMP DIVIDER]
dCF
*
(1)
[Ramp divider]
0 to 10
4
The ramp that is enabled (
[De ce le ration]
(dEC)
or
[De ce le ration 2]
(dE2)
) is then divided by this coefficient when stop
requests are sent.
Value 0 corresponds to a minimum ramp time.
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......