Configuration Mode (ConF)
195
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
bIr
[Brake release freq]
[Auto]
(AUtO)
to 10 Hz
[Auto]
(AUtO)
*
Brake release frequency threshold (initialization of acceleration ramp).
This parameter can be accessed if
[M ove m e nt type ]
(bSt)
page
194
is set to
[Hois ting]
(UEr)
.
[Auto]
(AUtO)
: The drive takes a value equal to the rated slip of the motor, calculated using the drive parameters
0 to 10 Hz
: Manual control.
(1)
AUtO
bEn
[Brake engage freq]
[Auto]
(AUtO)
0 to 10 Hz
[Auto]
(AUtO)
*
Brake engage frequency threshold.
Note :
[Brak e e ngage fre q]
(bEn)
cannot be higher than
[Low s pe e d]
(LSP)
.
[Auto]
(AUtO)
: The drive takes a value equal to the rated slip of the motor, calculated using the drive parameters
0 to 10 Hz
: Manual control.
(1)
AUtO
tbE
[Brake engage delay]
0 to 5.00 s
0 s
*
Time delay before request to engage brake.
(1)
bEt
[Brake engage time]
0 to 5.00 s
0 s
g
Brake engage time (brake response time).
(1)
SdC1
[Auto DC inj. level 1]
0 to 1.2 In (2)
0.7 In (2)
*
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected m otor is properly rated for the DC injection current to be applied in term s of amount
and tim e in order to avoid overheating and dam age to the m otor.
Failure to follow these instructions can result in equipment damage.
Level of standstill DC injection current.
Note :
This parameter can be accessed if
[M ove m e nt type ]
(bSt)
page
194
is set to
[Trave ling]
(HOr)
.
(1)
bEd
*
nO
YES
[Engage at reversal]
[No]
(
nO
)
Can be used to select w hether or not the brake engages on transition to zero speed w hen the operating direction is reversed.
[No]
(nO)
: The brake does not engage
[Ye s ]
(YES)
: The brake engages
JdC
[Jump at reversal]
[Auto]
(AUtO)
to 10 Hz
[Auto]
(AUtO)
*
This parameter can be accessed if
[M ove m e nt type ]
(bSt)
page
194
is set to
[Hois ting]
(UEr)
.
[Auto]
(AUtO)
: The drive takes a value equal to the rated slip of the motor, calculated using the drive parameters
0 to 10 Hz
: Manual control
When the reference direction is reversed, this parameter can be used to avoid loss of torque (and consequential release of load)
on transition to zero speed. Parameter is not applicable if
[Engage at re ve rs al]
(bEd)
=
[Ye s ]
(YES)
.
(1)
AUtO
-
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FUN- > BLC-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...