Configuration Mode (ConF)
173
STOP CONFIGURATION
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FUn-
[APPLICATION FUNCT.]
(continued)
Stt-
[STOP CONFIGURATION]
Note :
Some types of stops cannot be used w ith all other functions. Follow the instructions on page
163
.
Stt
rMP
FSt
nSt
dCI
[Type of stop]
[Ram p s top]
(rMP)
Stop mode on disappearance of the run command or appearance of a stop command.
Note :
If the "brake logic" function on page
194
has been enabled, or if
[Low s peed time out]
(tLS)
page
95
or
213
is not 0,
only ramp type stops may be configured.
[Ram p s top]
(rMP)
: Stop on ramp
[Fas t s top]
(FSt)
: Fast stop
[Free w he e l]
(nSt)
: Freew heel stop
[DC inject io n]
(dCI)
: DC injection stop. Available only if
[M otor control type]
(Ctt)
page
105
is not set to
[Sync. m ot.]
(SYn)
.
FFt
*
(1)
[Freewheel stop Thd.]
0.2 to 599 Hz
0.2 Hz
Speed threshold below which the motor w ill sw itch to freewheel stop.
This parameter supports sw itching from a ramp stop or a fast stop to a freew heel stop below a low speed threshold.
This parameter can be accessed if
[Type of s top]
(Stt)
is set to
[Fas t s top]
(FSt)
or
[Ram p s top]
(rMP)
and if
[Brak e
as s ignm e nt]
(bLC)
or
[Auto DC inje ction]
(AdC)
are configured.
nSt
nO
LI1
...
[Freewheel stop ass.]
[No]
(nO)
The stop is activated w hen the input or the bit changes to 0. If the input returns to state 1 and the run command is still active, the
motor will only restart if
[2/3 wire contro l]
(tCC)
page
85
is set to
[2 wire ]
(2C)
and if
[2 wire type]
(tCt)
is set to
[Le ve l]
(LEL)
or
[Fw d priority]
(PFO)
. If not, a new run command must be sent.
[No]
(nO)
: Not assigned
[LI1]
(LI1)
: Logical input LI1
[...]
(...)
: See the assignment conditions on page
153
FSt
nO
LI1
...
[Fast stop assign.]
[No]
(nO)
The stop is activated w hen the input changes to 0 or the bit changes to 1 (bit in
[I/O profile ]
(IO)
at 0).
If the input returns to state 1 and the run command is still active, the motor w ill only restart if
[2/3 w ire
control]
(tCC)
page
85
is set to
[2 wire ]
(2C)
and if
[2 wire type]
(tCt)
is set to
[Level]
(LEL)
or
[Fwd priority ]
(PFO)
.
If not, a new run command must be sent.
Note :
This function cannot be used w ith certain other functions. Follow the instructions on page
163
.
[No]
(nO)
: Not assigned
[LI1]
(LI1)
: Logical input LI1
[...]
(...)
: See the assignment conditions on page
153
dCF
*
(1)
[Ramp divider]
0 to 10
4
This paramet er can be accessed if
[Type of stop]
(Stt)
is set to
[Fast stop]
(FSt)
and if
[Fast stop assign.]
(FSt)
is not
[No]
(nO)
and if
[Stop type ]
(PAS)
is set to
[Fas t s top]
(FSt)
.
The ramp that is enabled (
[De ce le ration]
(dEC)
or
[De ce le ration 2]
(dE2)
) is then divided by this coefficient when stop
requests are sent.
Value 0 corresponds to a minimum ramp time.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FUN- > STT-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...