Configuration Mode (ConF)
266
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FLt-
[FAULT MANAGEMENT]
(continued)
FqF-
[FREQUENCY METER]
FqF
nO
YES
[Frequency meter]
[No]
(nO)
Activation of the speed measurement function.
[No]
(nO)
: Function inactive. In this case, none of the function parameters can be accessed
[Ye s ]
(YES)
: Function active, assignment only possible if no other functions have been assigned to the "Pulse input" input
FqC
[Pulse scal. divisor]
1.0 to 100.0
1.0
Scaling factor for the "Pulse input" input (divisor). The frequency measured is displayed by means of the
[Puls e in. w ork . fre q.]
(FqS)
parameter, page
50
.
FqA
nO
-
[Overspd. pulse thd.]
[No]
(nO)
Activation and adjustment of overspeed monitoring:
[Ove rspeed]
(SOF)
.
[No]
(nO)
: No overspeed monitoring
1 Hz to 20.00 k Hz
: Adjustment of the frequency tripping threshold on the "Pulse input" input divided by
[Puls e s cal. divis or]
(FqC)
.
tdS
[Pulse overspd delay]
0.0 s to 10.0 s
0.0 s
Time delay for taking overspeed detected fault into account.
Fdt
nO
-
[Level fr. pulse ctrl]
[No]
(nO)
Activation and adjustment of monitoring for the Pulse input (speed feedback):
[Speed fdback loss]
(SPF)
.
[No]
(nO)
: No monitoring of speed feedback
0.1 Hz to 599 Hz
: Adjustment of the motor frequency threshold for tripping a speed feedback detected fault (difference between
the estimated frequency and the measured speed).
Fqt
nO
-
[Pulse thd. wo Run]
[No]
(nO)
Activation and adjustment of brake monitoring:
[Brak e fe e dback ]
(brF)
.
If brake logic control
[Brak e as s ignm e nt]
(bLC)
page
194
is not configured, this parameter is forced to
[No]
(nO)
.
[No]
(nO)
: No brake monitoring
1 Hz to 1,000 Hz
: Adjustment of the motor frequency threshold.
tqb
[Pulse wo Run delay]
0.0 s to 10.0 s
0.0 s
Time delay for taking brake monitoring into account.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FLT- > FQF-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...