Configuration Mode (ConF)
277
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
COM-
[COMMUNICATION]
(continued)
CnO-
[CANopen]
AdCO
OFF
-
[CANopen address]
[OFF]
(OFF)
to 127
[OFF]
(OFF)
[OFF]
(OFF)
: OFF
1 to 127
bdCO
50
125
250
500
IM
[CANopen bit rate]
[250 k bps ]
(250)
[50 k bps ]
(50)
: 50,000 Bauds
[125 k bps ]
(125)
: 125,000 Bauds
[250 k bps ]
(250)
: 250,000 Bauds
[500 k bps ]
(500)
: 500,000 Bauds
[1 M bps ]
(1M)
: 1 MBauds
ErCO
[Error code]
0 to 5
-
Read-only parameter, cannot be modified.
COM-
[COMMUNICATION]
(continued)
Cbd-
[COMMUNICATION CARD]
See the specific documentation for the card used.
LCF-
[FORCED LOCAL]
FLO
nO
LI1
...
LI6
LAI1
LAI2
OL01
...
OL10
[Forced local assign.]
[No]
(nO)
Forced local assignment.
Forced local mode is active w hen the input is at state 1.
[Force d local as s ign.]
(FLO)
is forced to
[No]
(nO)
if
[Profile ]
(CHCF)
is set to
[I/O profile ]
(IO)
page
154
.
[No]
(nO)
: Function inactive
[LI1]
(LI1)
: Logical input LI1
...
[LI6]
(LI6)
: Logical input LI6
[LAI1]
(LAI1)
: Logical input AI1
[LAI2]
(LAI2)
: Logical input AI2
[OL01]
(OL01)
: Function blocks: Logical Output 01
...
[OL10]
(OL10)
: Function blocks: Logical Output 10
FLOC
nO
AI1
AI2
AI3
LCC
PI
OA01
...
OA10
[Forced local Ref.]
[No]
(nO)
Forced local reference source assignment.
[No]
(nO)
: Not assigned (control via the terminals w ith zero reference)
[AI1]
(AI1)
: Analog input
[AI2]
(AI2)
: Analog input
[AI3]
(AI3)
: Analog input
[HM I]
(LCC)
: Assignment of the reference and command to the graphic display terminal or remote display terminal.
Reference:
[HM I Fre quency ref.]
(LFr)
page
50
.
Command: RUN/STOP/FWD/REV keys.
[RP]
(PI)
: Pulse input
[OA01]
(OA01)
: Function blocks: Analog Output 01
...
[OA10]
(OA10)
: Function blocks: Analog Output 10
FLOt
*
[Time-out forc. local]
0.1 to 30 s
10.0 s
0.1 to 30 s.
This parameter can be accessed if
[Forced local as sign.]
(FLO)
is not set to
[No]
(nO)
.
Time delay before communication monitoring is resumed on leaving forced local mode.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
*
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...