Configuration Mode (ConF)
104
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FFM
Std
rUn
StP
[Fan Mode]
[Standard]
(Std)
If
[Fan Mode]
(FFM)
is s et to
[Never]
(Stp)
, the fan of the drive is dis abled.
Service life of electronic com ponent is reduced.
NOTICE
DAMAGE TO THE DRIVE
The am bient tem perature m ust be lim ited to 40°C (104°F)
Failure to follow these instructions can result in equipment damage.
[Standard]
(Std)
: The fan starts and stops automatically according to the drive thermal state
[Alw ays ]
(rUn)
: The fan is started
[Ne ve r]
(Stp)
: The fan is stopped
SdS
[Scale factor display]
0.1 to 200
30
Used to display a value in proportion to the output frequency
[Output frequenc y]
(rFr)
: the machine speed, the motor speed, etc.
The display w ill show
[Cust. output value]
(SPd3)
=
[Scale factor display]
(SdS)
x
[Output frequenc y]
(rFr)
to 2 decimal places
1000
•
If
[Scale factor display]
(SdS)
y
1,
[Cust. output value]
(SPd1)
is displayed (possible definition = 0.01)
•
If 1 <
[Scale factor display]
(SdS)
y
10,
[Cust. output value]
(SPd2)
is displayed (possible definition = 0.1)
•
If
[Scale factor display]
(SdS)
> 10,
[Cust. output value]
(SPd3)
is displayed (possible definition = 1)
•
If
[Scale factor display]
(SdS)
> 10 and
[Scale factor display]
(SdS)
x
[Output frequency]
(rFr)
> 9,999:
example: for 24,223, display w ill show 24.22
- If
[Scale factor display]
(SdS)
> 10 and
[Scale factor display]
(SdS)
x
[Output frequency]
(rFr)
> 65,535, display
locked at 65.54
Example: Display motor speed for
4-pole motor, 1,500 rpm at 50 Hz (synchronous speed):
[Scale factor display]
(SdS)
= 30
[Cust. output value]
(SPd3)
= 1,500 at
[Output frequenc y]
(rFr)
= 50 Hz
(1) In corresponds to the rated drive current indicated in the Installation manual or on the drive nameplate.
(2) If a graphic display terminal is not in use, values greater than 9,999 w ill be displayed on the 4-digit display w ith a period
mark after the thousand digit, example: 15.65 for 15,650.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Parameter that can be modified during operation or w hen stopped.
To change the assignment of this parameter, press the ENT key for 2 s.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > DRC-
2 s
*
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...