Configuration Mode (ConF)
128
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
USI
dSI
IL01
...
IL10
FbrM
SLS1
SLS2
SS11
SS12
StO1
StO2
SMS1
SMS2
[+s pe e d around ref.]
(USI)
: + Speed around ref
[-s pe e d around ref.]
(dSI)
: - Speed around ref
[IL01]
(IL01)
: Function blocks: Logical Input 1
...
[IL10]
(IL10)
: Function blocks: Logical Input 10
[FB s tart]
(FbrM)
: Function blocks: Run mode
[SLS ch.1]
(SLS1)
: SLS safety function Channel 1
[SLS ch.2]
(SLS2)
: SLS safety function Channel 2
[SS1 ch.1]
(SS11)
: SS1 safety function Channel 1
[SS1 ch.2]
(SS12)
: SS1 safety function Channel 2
[STO ch.1]
(St01)
: STO safety function Channel 1
[STO ch.2]
(St02)
: STO safety function Channel 2
[SM S ch.1]
(SMS1)
: SMS safety function Channel 1
[SM S ch.2]
(SMS2)
: SMS safety function Channel 2
Note :
Safety function channels are available for LI3-LI4 and LI5-LI6 only.
L1d
[LI1 On Delay]
0 to 200 ms
0 ms
This parameter is used to take account of the change of the logic input to state 1 w ith a delay that can be adjusted betw een 0
and 200 milliseconds, in order to filter out possible interference. The change to state 0 is taken into account w ithout delay.
I_O-
[INPUTS / OUTPUTS CFG]
(continued)
L2-
to
L6-
[LIx CONFIGURATION]
All the logic inputs available on the drive are processed as in the example for LI1 above, up to LI6.
L5-
[LI5 CONFIGURATION]
Specific parameters for LI5 used as a pulse input.
PIA
[RP assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with the Pulse input in order to check, for example, for compatibility problems.
Identical to
[AI1 as s ignm e nt]
(A11A)
page
133
.
PIL
[RP min value]
0 to 20.00 kHz
0 kHz
Pulse input scaling parameter of 0% in Hz * 10 unit.
PFr
[RP max value]
0 to 20.00 kHz
20.00 kHz
Pulse input scaling parameter of 100% in Hz * 10 unit.
PFI
[RP filter]
0 to 1,000 ms
0 ms
I/O ext Pulse input cutoff time of the low -filter.
LA1-
LA2-
[LAx CONFIGURATION]
The 2 analog inputs AI1 and AI2 on the drive could be used as LI inputs and are processed as in the example for LI1 above.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
To change the assignment of this parameter, press the ENT key for 2 s.
2 s
*
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...