Configuration Mode (ConF)
262
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
Behavior of the drive in the event of a communication interruption w ith a communication card.
nO
[Ignore]
(nO)
: Detected fault ignored
YES
[Fre e w heel]
(YES)
: Freew heel stop
Stt
[Per STT]
(Stt)
: Stop according to configuration of
[Type of stop]
(Stt)
page
173
, without fault tripping. In this case, the
fault relay does not open and the drive is ready to restart as soon as the detected fault disappears, according to the restart
conditions of the active command channel (for example, according to
[2/3 wire control]
(tCC)
and
[2 wire type]
(tCt)
page
125
if control is via the terminals). Configuring an alarm for this detected fault is recommended (assigned to a logic output, for
example) in order to indicate the cause of the stop
LFF
[Fallback s pd]
(LFF)
: Change to fallback speed, maintained as long as the detected fault persists and the run command has
not been removed (1)
rLS
[Spd m aint.]
(rLS)
: The drive maintains the speed being applied w hen the detected fault occurred, as long as the detected
fault is present and the run command has not been removed (1)
rMP
[Ram p s top]
(rMP)
: Stop on ramp
FSt
[Fas t s top]
(FSt)
: Fast stop
dCI
[DC inje ction]
(dCI)
: DC injection stop. This type of stop cannot be used w ith certain other functions. See table on page
163
COL
[CANopen fault mgt]
[Fre e w heel]
(YES)
nO
WARNING
LOSS OF CONTROL
If this param eter is s et to
[Ignore]
(nO)
, CANopen com m unication m onitoring is dis abled.
•
Only us e this s etting after a thorough ris k as s essment in com pliance with all regulations and s tandards
that apply to the device and to the application.
•
Only us e this s etting for tes ts during commissioning.
•
Verify that com m unication m onitoring has been re-enabled before com pleting the com missioning
procedure and perform ing the final com missioning tes t.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Behavior of the drive in the event of a communication interruption w ith integrated CANopen®.
[Ignore]
(nO)
: Detected fault ignored
[Fre e w heel]
(YES)
: Freew heel stop
[Per STT]
(Stt)
: Stop according to configuration of
[Type of stop]
(Stt)
page
173
, without fault tripping. In this case, the
fault relay does not open and the drive is ready to restart as soon as the detected fault disappears, according to the restart
conditions of the active command channel (for example, according to
[2/3 wire control]
(tCC)
and
[2 wire type]
(tCt)
page
125
if control is via the terminals). Configuring an alarm for this detected fault is recommended (assigned to a logic output, for
example) in order to indicate the cause of the stop.
[fallback s pd]
(LFF)
: Change to fallback speed, maintained as long as the detected fault persists and the run command has
not been removed (1)
[Spd m aint.]
(rLS)
: The drive maintains the speed being applied w hen the detected fault occurred, as long as the detected
fault is present and the run command has not been removed (1)
[Ram p s top]
(rMP)
: Stop on ramp
[Fas t s top]
(FSt)
: Fast stop
[DC inje ction]
(dCI)
: DC injection stop. This type of stop cannot be used w ith certain other functions. See table on page
165
.
YES
Stt
LFF
rLS
rMP
FSt
dCI
SLL
[Modbus fault mgt]
[Fre e w heel]
(YES)
WARNING
LOSS OF CONTROL
If this param eter is s et to
[Ignore]
(nO)
, Modbus com m unication m onitoring is disabled.
•
Only us e this s etting after a thorough ris k as s essment in com pliance with all regulations and s tandards
that apply to the device and to the application.
•
Only us e this s etting for tes ts during commissioning.
•
Verify that com m unication m onitoring has been re-enabled before com pleting the com missioning
procedure and perform ing the final com missioning tes t.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FLT- > CLL-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...