Configuration Mode (ConF)
177
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
SdC2
[Auto DC inj. level 2]
0 to 1.2 In (2)
0.5 In (2)
*
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected m otor is properly rated for the DC injection current to be applied in term s of am ount
and tim e in order to avoid overheating and dam age to the m otor.
Failure to follow these instructions can result in equipment damage.
2nd level of standstill DC injection current.
This parameter can be accessed if
[Auto DC inje ction]
(AdC)
is not
[No]
(nO)
.
(1)
tdC2
[Auto DC inj. time 2]
0 to 30 s
0 s
*
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected m otor is properly rated for the DC injection current to be applied in term s of am ount
and tim e in order to avoid overheating and dam age to the m otor.
Failure to follow these instructions can result in equipment damage.
2nd standstill injection time.
This parameter can be accessed if
[Auto DC inje ction]
(AdC)
is set to
[Ye s ]
(YES)
.
(1)
(1) The parameter can also be accessed in the
[SETTINGS]
(SEt-)
menu.
(2) In corresponds to the rated drive current indicated in the Installation manual and on the drive nameplate.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Parameter that can be modified during operation or w hen stopped.
To change the assignment of this parameter, press the ENT key for 2 s.
2 s
*
AdC
SdC2
Operation
YES
x
I
SdC1
SdC2
tdC1
tdC1 + tdC2 t
I
SdC1
SdC2
tdC1
t
I
SdC1
t
1
0
t
0
t
Ct
≠
0
Ct
= 0
Run command
Speed
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...