Configuration Mode (ConF)
246
SCL3
[Ground short circuit]
[Fre e w heel]
(
YES
)
nO
Direct ground short-circuit fault detection behaviour
Can be accessed for drives rating ER24-5.5
… -15.0/4K/B.
Visible if
[3.1 ACCESS LEVEL]
(LAC)
is set to
[Expe rt]
(Epr)
and
[DC-Bus chaining]
(dCCM)
above is not set to
[No]
(nO)
.
[Ignore]
(nO)
: Detected fault ignored
[Fre ewheel]
(YES)
: Detected fault w ith freewheel stop
[Ground s hort circuit]
(SCL3)
is forced to
[Ignore ]
(nO)
for ER24-5.5
… -15.0/4K/B
drives if
[DC-Bus chaining]
(dCCM)
above is set to
[Bus & M ain]
(MAIn)
.
Note
: If
[Ground s hort circuit]
(SCL3)
is set to
[Ignore ]
(nO)
, integrated safety functions (except Safe Torque Off ) for
ER24-5.5
… -15.0/4K
drives cannot be used, otherw ise the drive w ill trigger in
[Safe function fault]
(SAFF)
state.
DANGER
GROUND FAULT MONITORING DISABLED, NO ERROR DETECTION
Setting this param eter to
[Ignore]
(nO)
deactivates ground fault m onitoring.
•
Only us e this parameter after a thorough risk assessment in com pliance with all regulations and s tandards
that apply to the device and to the application.
•
Im plem ent alternative ground fault m onitoring functions that do not trigger automatic error responses of the
drive, but allow for adequate, equivalent res ponses by other m eans in com pliance with all applicable
regulations and s tandards as well as the ris k as sessment.
•
Com m ission and tes t the s ys tem with ground fault m onitoring enabled.
•
During com m issioning, verify that the drive and the s ys tem operate as intended by perform ing tes ts and
s im ulations in a controlled environment under controlled conditions.
Failure to follow these instructions will result in death or serious injury.
YES
*
UrES
[Mains Voltage]
Rated voltage of the supply mains in Vac.
According to drive
voltage rating
According to drive
voltage rating
*
Visible if
[3.1 ACCESS LEVEL]
(LAC)
is set to
[Expe rt]
(Epr)
and
[DC-Bus chaining]
(dCCM)
above is set to
[No]
(
nO
)
.
For ER24…K (B):
[200V ac]
(200)
: 200 Volts AC
[220V ac]
(220)
: 220 Volts AC
[230V ac]
(230)
: 230 Volts AC
[240V ac]
(240)
: 240 Volts AC (factory setting)
[Le xium ]
(LHM)
:
[M ains voltage ]
(UrES)
,
[Unde rvoltage le ve l]
(
USL
)
,
[Brak ing le ve l]
(Ubr)
are forced to their default
value.
For ER24…/4K (B):
[380V ac]
(380)
: 380 Volts AC
[400V ac]
(400)
: 400 Volts AC
[440V ac]
(440)
: 440 Volts AC
[460V ac]
(460):
460 Volts AC
[500V ac]
(500)
: 500 Volts AC (factory setting)
[Le xium ]
(LHM)
:
[M ains voltage ]
(UrES)
,
[Unde rvoltage le ve l]
(USL)
are forced to their default value,
[Brak ing le ve l]
(Ubr)
is forced to 780 Vdc and the drive w ill trigger in
[Ove rbraking]
(ObF)
at a DC Bus level of 820 Vdc instead of 880 Vdc
200
220
230
240
LHM
380
400
440
460
500
LHM
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > DCC-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...