Configuration Mode (ConF)
135
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
AI3S
[AI3 Interm. point Y]
0 to 100%
0%
Output delinearization point coordinate (frequency reference).
Percentage of the internal frequency reference corresponding to the
[AI3 Inte rm . point X]
(A13E)
percentage of physical
input signal.
I_O-
[INPUTS / OUTPUTS CFG]
(continued)
AU1-
[VIRTUAL AI1]
AU1A
[AIV1 assignment]
Virtual analog input 1 via the jog dial available on the front side of the product.
Identical to
[AI1 as s ignm e nt]
(A11A)
page
133
.
AU2-
[VIRTUAL AI2]
AU2A
[AIV2 assignment]
Possible assignments for
[AI virtual 2]
(AIU2)
: Virtual analog input 2 via communication channel, to be configured w ith
[AI2
ne t. channe l]
(AIC2)
.
Identical to
[AIV1 as s ignment]
(AU1A)
page
133
.
AIC2
*
nO
Mdb
CAn
nEt
[AI2 net. Channel]
[No]
(nO)
[VIRTUAL AI2]
(AU2A)
source channel.
This parameter can also be accessed in the
[PID REGU LA TO R]
(
PId-
)
submenu page
210
.
Scale: The value 8192 transmitted by this input is equivalent to 10 V on a 10 V input.
[No]
(nO)
: Not assigned
[M odbus ]
(Mdb)
: Integrated Modbus
[CANope n]
(CAn)
: Integrated CANopen®
[Com . card]
(nEt)
: Communication card (if inserted)
IEn-
[ENCODER CONFIGURATION]
Follow ing parameters can be accessed if the speed monitoring card has been inserted.
EnU
nO
SEC
[Encoder usage]
[No]
(nO)
[No]
(nO)
: Function inactive.
[Fdbk monit.]
(SEC)
: The encoder provides speed feedback for monitoring.
EnS
*
AAbb
Ab
[Encoder type]
[AABB]
(AAbb)
Encoder usage configuration.
Encoder usage configuration.
To be configured in accordance with the type of encoder used.
[AABB]
(AAbb)
: For signals A, /A, B, /B.
[AB]
(Ab)
: For signals A, B.
Follow ing parameters can be accessed if
[Encoder usage]
(EnU)
is set to
[Fdbk monit.]
(SEC)
.
PGI
*
[Number of pulses]
100 to 3600
1024
Encoder usage configuration.
Number of pulses per encoder revolution.
Follow ing parameters can be accessed if
[Encoder usage]
(EnU)
is set to
[Fdbk monit.]
(SEC)
.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > I_O- > IEn-
*
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...