Configuration Mode (ConF)
125
Inputs / outputs CFG
The param eters in the
[INPUTS / OUTPUTS CFG]
(I_O-)
m enu can only be m odified when the drive is
s topped and no run com m and is present.
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FULL
[FULL]
(continued)
I_O-
[INPUTS / OUTPUTS CFG]
tCC
2 s
2C
3C
[2/3 wire control]
[2 w ire ]
(2C)
WARNING
UNANTICIPATED EQUIPMENT OPERATION
If this param eter is changed, the param eters
[Reverse assign.]
(rrS)
and
[2 wire type]
(tCt)
and the
as s ignm ents of the digital inputs are res et to the factory s etting.
Verify that this change is com patible with the type of wiring us ed.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
[2 w ire ]
(2C)
2- w ire control (le vel commands):
This is the input state (0 or 1) or edge (0 to 1 or 1 to 0) w hich controls running or stopping.
Example of "source" w iring:
+24 LI1 LIx
LI1: forward
LIx: reverse
[3 w ire ]
(3C)
3- w ire control (pulse commands):
A "forward" or "reverse" pulse is sufficient to command starting, a "stop" pulse is sufficient
to command stopping.
Example of "source" w iring:
+24 LI1 LI2 LIx
LI1: stop
LI2: forward
LIx: reverse
tCt
*
2 s
LEL
trn
PFO
[2 wire type]
[Trans it io n]
(trn)
WARNING
UNANTICIPATED EQUIPMENT OPERATION
Verify that the param eter s etting is com patible with the type of wiring us ed.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
[Le ve l]
(LEL)
: State 0 or 1 is taken into account for run (1) or stop (0)
[Trans it ion]
(trn)
: A change of state (transition or edge) is necessary to initiate operation, in order to avoid accidental restarts
after a break in the pow er supply
[Fw d priority]
(PFO)
: State 0 or 1 is taken into account for run or stop, but the "forward" input takes priority over the "reverse"
input
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > I_O-
ER24
ER24
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...