Configuration Mode (ConF)
174
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
dCI
[DC injection assign.]
[No]
(nO)
nO
WARNING
UNINTENDED MOVEMENT
•
Do not us e DC injection to generate holding torque when the m otor is at a s tands till.
•
Us e a holding brake to keep the m otor in the s tands till pos ition.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
DC injection braking is initiated w hen the assigned input or bit changes to state 1.
If the input returns to state 0 and the run command is still active, the motor w ill only restart if
[2/3 w ire control]
(tCC)
page
85
is set to
[2 wire]
(2C)
and if
[2 wire type]
(tCt)
is set to
[Level]
(LEL)
or
[Fwd priorit y]
(PFO)
. If not, a new run comm and
must be sent.
Note :
This function cannot be used w ith certain other functions. Follow the instructions on page
163
.
[No]
(nO)
: Not assigned
[LI1]
(LI1)
: Logical input LI1
[...]
(...)
: See the assignment conditions on page
153
LI1
...
IdC
[DC inject. level 1]
0.1 to 1.41 In (2)
0.64 In (2)
*
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected m otor is properly rated for the DC injection current to be applied in term s of am ount
and tim e in order to avoid overheating and dam age to the m otor.
Failure to follow these instructions can result in equipment damage.
Level of DC injection braking current activated via logic input or selected as stop mode.
This parameter can be accessed if
[Type of stop]
(Stt)
is set to
[DC inje ction]
(dCI)
or if
[DC inje ction as sign.]
(dCI)
is not
[No]
(nO)
.
(1) (3)
tdI
[DC injection time 1]
0.1 to 30 s
0.5 s
*
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected m otor is properly rated for the DC injection current to be applied in term s of am ount
and tim e in order to avoid overheating and dam age to the m otor.
Failure to follow these instructions can result in equipment damage.
Maximum current injection time
[DC inje ct. le vel 1]
(IdC)
. After this time, the injection current becomes
[DC inje ct. le ve l 2]
(IdC2)
.
This parameter can be accessed if
[Type of stop]
(Stt)
is set to
[DC inje ction]
(dCI)
or if
[DC inje ction as sign.]
(dCI)
is not
set to
[No]
(nO)
.
(1) (3)
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FUN- > STT-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...