Configuration Mode (ConF)
138
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
I_O-
[INPUTS / OUTPUTS CFG]
(continued)
r1-
[R1 CONFIGURATION]
r1
[R1 Assignment]
[No drive flt]
(FLt)
nO
[No]
(nO)
: Not assigned
[No drive flt]
(FLt)
: Drive fault detection status (relay normally energized, and de-energized in the event of an error)
[Drv running]
(rUn)
: Drive running
[Fre q. Th. attain.]
(FtA)
: Frequency threshold attained (
[Fre q. thre s hold]
(Ftd)
page
102
)
[HSP attain.]
(FLA)
: High speed attained
[I attaine d]
(CtA)
: Current threshold attained (
[Curre nt thre s hold]
(Ctd)
page
102
)
[Fre q.re f.att]
(SrA)
: Frequency reference attained
[Th.m ot. att.]
(tSA)
: Motor 1 thermal state attained
[PID e rror al]
(PEE)
: PID error alarm
[PID fdbk al]
(PFA)
: PID feedback alarm
[Fre q. Th. 2 attaine d]
(F2A)
: Frequency threshold 2 attained (
[Fre q. thre s hold 2]
(F2d)
page
102
)
[Th. drv. att.]
(tAd)
: Drive thermal state attained
[Pro.Undload]
(ULA)
: Underload alarm
[Ovld.P.Alrm ]
(OLA)
: Overload alarm
[Rope s lack ]
(rSdA)
: Rope slack (see
[Rope s lack config.]
(rSd)
parameter page
205
)
[High tq. att.]
(ttHA)
: Motor torque overshooting high threshold
[High torque thd.]
(ttH)
page
102
[Low tq. att.]
(ttLA)
: Motor torque undershooting low threshold
[Low torque thd.]
(ttL)
page
102
[Forw ard]
(MFrd)
: Motor in forw ard rotation
[Re ve rs e ]
(MrrS)
: Motor in reverse rotation
[Th.m ot2 att]
(tS2)
: Motor 2 thermal threshold (TTD2) reached
[Th.m ot3 att]
(tS3)
: Motor 3 thermal threshold (TTD3) reached
[Ne g Torque ]
(AtS)
: Negative torque (braking)
[Cnfg.0 act.]
(CnF0)
: Configuration 0 active
[Cnfg.1 act.]
(CnF1)
: Configuration 1 active
[Cnfg.2 act.]
(CnF2)
: Configuration 2 active
[Se t 1 active ]
(CFP1)
: Parameter set 1 active
[Se t 2 active ]
(CFP2)
: Parameter set 2 active
[Se t 3 active ]
(CFP3)
: Parameter set 3 active
[DC charge d]
(dbL)
: DC bus charging
[In brak ing]
(brS)
: Drive braking
[P. re moved]
(PrM)
: Drive locked by "Safe Torque Off" input
[Fr.m e t. alar.]
(FqLA)
: Measured speed threshold attained
[Puls e w arning thd.]
(FqL)
page
102
[I pre s ent]
(
MCP
)
:
Motor current present
[Lim it sw. att]
(LSA)
: Limit sw itch attained
[Load alarm ]
(dLdA)
: Load variation detection (see page
267
)
[Alarm Grp 1]
(AGI)
: Alarm group 1
[Alarm Grp 2]
(AG2)
: Alarm group 2
[Alarm Grp 3]
(AG3)
: Alarm group 3
[LI6=PTC al.]
(PLA)
: LI6 = PTCL alarm
[Ext. fault al]
(EFA)
: External fault alarm
[Unde r V. al.]
(USA)
: Undervoltage alarm
[Uvolt w arn]
(UPA)
: Undervoltage threshold
[Al. °C drv]
(tHA)
: Drive overheating
[Lim T/I att.]
(SSA)
: Torque limit alarm
[IGBT al.]
(tJA)
: Thermal junction alarm
[AI3 Al. 4-20]
(AP3)
: Al3 4-20 mA loss alarm
[Re ady]
(rdY)
: Ready to start
FLt
rUn
FtA
FLA
CtA
SrA
tSA
PEE
PFA
F2A
tAd
ULA
OLA
rSdA
ttHA
ttLA
MFrd
MrrS
tS2
tS3
AtS
CnF0
CnF1
CnF2
CFP1
CFP2
CFP3
dbL
brS
PrM
FqLA
MCP
LSA
dLdA
AG1
AG2
AG3
PLA
EFA
USA
UPA
tHA
SSA
tJA
AP3
rdY
r1-
[R1 CONFIGURATION]
(continued)
r1d
(1)
[R1 Delay time]
0 to 60,000 ms
0 ms
The change in state only takes effect once the configured time has elapsed, w hen the information becomes true.
The delay cannot be set for the
[No drive flt]
(FLt)
assignment, and remains at 0.
r1S
POS
nEG
[R1 Active at]
[1]
(POS)
Configuration of the operating logic:
[1]
(POS)
: State 1 w hen the information is true
[0]
(nEG)
: State 0 w hen the information is true
Configuration
[1]
(POS)
cannot be modified for the
[No drive flt]
(FLt)
assignment.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > I_O- > R1-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...