Configuration Mode (ConF)
106
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
UF5
SYn
UFq
nLd
[V/F 5pts ]
(UF5)
: 5-segment V/F profile: As
[Standard]
(Std)
profile but also supports the avoidance of resonance
(saturation).
Voltage
UnS
U5
The profile is defined by the
U4
values of parameters UnS, FrS,
U0 to U5 and F1 to F5.
U3
U1
FrS > F5 > F4 > F3 > F2 > F1
U2
U0
Frequency
F1
F2
F3
F4 F5
FrS
Note :
U0 is the result of an internal calculation based on motor parameters and multiplied by UFr (%). U0 can be adjusted by
modifying UFr value.
[Sync. m ot.]
(SYn)
: For synchronous permanent magnet motors w ith sinusoidal electromotive force (EMF) only. This selection
makes the asynchronous motor parameters inaccessible, and the synchronous motor parameters accessible.
[V/F Quad.]
(UFq)
: Variable torque. For pump and fan applications.
[Ene rgy Sav.]
(nLd)
: Energy saving. For applications that do not require high dynamics.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > DRC- > ASY-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...