Configuration Mode (ConF)
107
Asynchronous motor parameters
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
ASY-
[ASYNC. MOTOR]
Only visible if
[Mot or control type]
(Ctt)
page
105
is not set to
[Sync. mot.]
(SYn)
.
nPr
*
[Rated motor power]
According to drive rating According to drive rating
This parameter cannot be accessed if
[Motor contro l type]
(Ctt)
page
105
is set to
[Sync . mot.]
(SYn)
.
Rated motor pow er given on the nameplate, in kW if
[Standard m ot. fre q]
(bFr)
is set to
[50Hz IEC]
(50)
, in HP if
[Standard m ot. fre q]
(bFr)
is set to
[60Hz NEM A]
( 0)
.
COS
*
[Motor 1 Cosinus Phi]
0.5 to 1
According to drive rating
Nominal motor cos phi.
This parameter can be accessed if
[M otor param choice]
(MPC)
is set to
[M ot Cos ]
(COS)
.
UnS
*
[Rated motor volt.]
100 to 480 V
According to drive rating and
[Standard m ot. fre q]
(bFr)
This parameter cannot be accessed if
[Mot or contro l type]
(Ctt)
page
105
is set to
[Sync . mot.]
(SYn)
.
Rated motor voltage given on the nameplate.
nCr
*
[Rated mot. current]
0.25 to 1.5 In (1)
According to drive rating and
[Standard m ot. fre q]
(bFr)
This parameter cannot be accessed if
[Mot or contro l type]
(Ctt)
page
105
is set to
[Sync . mot.]
(SYn)
.
Rated motor current given on the nameplate.
FrS
*
[Rated motor freq.]
10 to 800 Hz
50 Hz
This parameter cannot be accessed if
[Mot or contro l type]
(Ctt)
page
105
is set to
[Sync . mot.]
(SYn)
.
Rated motor frequency given on the nameplate.
The factory setting is 50 Hz, or preset to 60 Hz if
[Standard m ot. freq]
(bFr)
is set to 60 Hz.
nSP
*
[Rated motor speed]
0 to 65,535 rpm
According to drive rating
This parameter cannot be accessed if
[Mot or contro l type]
(Ctt)
page
105
is set to
[Sync . mot.]
(SYn)
.
0 to 9,999 rpm then 10.00 to 65.53 krpm on the integrated display terminal.
If, rather than the rated speed, the nameplate indicates the synchronous speed and the slip in Hz or as a %, calculate the rated
speed as follow s:
Nominal speed = Synchronous speed x
100 - slip as a %
100
or
Nominal speed = Synchronous speed x
50 - slip in Hz
(50 Hz motors)
50
or
Nominal speed = Synchronous speed x
60 - slip in Hz
(60 Hz motors).
60
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > DRC- > ASY-
Summary of Contents for ER24 Series
Page 6: ...6 Table of Contents ...
Page 14: ...16 ...
Page 34: ...Overview 36 ...
Page 40: ...42 ...
Page 74: ...Monitoring Mode MOn 76 ...
Page 241: ......
Page 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Page 294: ...Interface ItF 294 ...
Page 298: ...298 Open Save as trA ...
Page 302: ...Multipoint Screen 302 ...
Page 304: ...304 ...
Page 306: ...Maintenance 306 ...
Page 316: ...Diagnostics and Troubleshooting 316 ...
Page 318: ...318 ...
Page 340: ...Index of Parameter Codes 340 ...
Page 343: ......
Page 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...