6 - PARAMETER DESCRIPTION
set to Over current until the current drops or the starter trips on an overload.
A shear pin function can be implemented by setting the delay to its minimum value.
See Also
Over Current Level parameter (PFN 01) on page 76.
Auto Reset parameter (PFN 23) on page 84.
Controlled Fault Stop Enable parameter (PFN 25) on page 85.
Relay Output Configuration parameters (I/O 10 - 15) on page 91.
Under Current Trip Level
PFN 03
LCD Display
Range
Off, 5 – 100 % of FLA
(Default: Off)
Description
If the MX
3
detects a one cycle, average current that is less than the level defined, an under current alarm
condition exists and any relays programmed as alarm will energize. The under current timer starts a delay
time. If the under current still exists when the delay time expires, the starter Under Current Trips (F34) and
any relay programmed as fault relay changes state.
The Under Current Trip is only active in the UTS state, Energy Saver state, Current follower or while in the
Phase Control mode.
A relay can be programmed to change state when an under current alarm condition is detected.
See Also
Under Current Time parameter (PFN 04) on page 77.
Auto Reset parameter (PFN 23) on page 84.
Controlled Fault Stop Enable parameter (PFN 25) on page 85.
Relay Output Configuration parameters (I/O 10 - 15) on page 91.
Under Current Trip Delay Time
PFN 04
LCD Display
Range
Off, 0.1 – 90.0 seconds
(Default: 0.1 sec)
Description
The Under Current Time parameter sets the period of time that the motor current must be less than the Under
Current Level (PFN 03) parameter before an under current fault and trip occurs.
If "Off" is selected, the under current timer does not operate and the starter does not trip. It energizes any
relay set to undercurrent until the current rises.
See Also
Under Current Level parameter (PFN 03) on page 77.
Relay Output Configuration parameters (I/O 10 - 15) on page 91.
Auto Reset parameter (PFN 23) on page 84.
Controlled Fault Stop Enable parameter (PFN 25) on page 85.
PFN: Undr Cur Lvl
03
Off
Alarm
Condition
Fault
Trip
% Current
Under Current Trip
Delay Time
PFN 04
Under Cur Level
PFN 03
Time
Motor FLA
QST 01
PFN: Undr Cur Tim
04
0.1
sec
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...