8 - TROUBLESHOOTING & MAINTENANCE
Fault Code
Description
Detailed Description of Fault / Possible Solutions
F35
Power Factor Leading
The motor power factor went above the PF leading trip level.
Verify loading of motor.
On synchronous motors, verify field supply current.
F36
Power Factor Lagging
The motor power factor went below the PF lagging trip level.
Verify loading of motor.
On synchronous motors, verify field supply current.
F37
Current Imbalance
A current imbalance larger than the Current Imbalance Trip Level parameter
setting (PFN 05) was present for longer than the Curr Imbal Trip Time (PFN 06).
Check motor wiring for cause of imbalance. (Verify dual voltage and 6 lead
motors for correct wiring configuration).
Check for large input voltage imbalances that can result in large current
imbalances.
Check motor for internal problems.
F38
Ground Fault
Ground current above the Ground Fault Trip level setting (PFN 07 / PFN 08) has
been detected for longer than the delay time (PFN 09) setting.
Check motor wiring for ground faults.
Check motor for ground faults.
Megger motor and cabling (disconnect from starter before testing).
Verify that the motor FLA (QST 01) and CT ratio (FUN 03) settings are correct.
Verify that the CTs are installed with all the White dots towards the input line.
In Single phase applications, verify that only two CTs are being used; that they are
installed with all the White dots or Xs in the correct direction; and that the CTs are
connected to the L1 and L3 CT inputs on the MX
3
control card.
F39
No Current at Run
Motor current went below 10% of FLA while the starter was running.
Verify Motor Connections.
Verify the CT wiring to the MX
3
control card.
Verify that the motor FLA (QST 01) and CT ratio (FUN 03) settings are correct.
Check if load is still connected to starter.
Check if motor may have been driven by the load (a regeneration condition).
Check Gate and Cathode connections to MX
3
for loose connections.
Check for inline contactor or disconnect.
F40
Shorted / Open SCR
A shorted or open SCR condition has been detected.
Verify that all SCR gate leads wires are properly connected at the SCR devices
and the MX
3
control card.
Check all SCRs with ohmmeter for shorts.
Verify that the Input Phase Sensitivity parameter setting (FUN 04) is correct.
Verify that the Starter Type parameter setting (FUN 07) is correct.
Verify the motor wiring. (Verify dual voltage motors for correct wiring
configuration).
F41
Current at Stop
Motor current was detected while the starter was not running.
Examine starter for shorted SCRs.
Examine bypass contactor (if present) to verify that it is open when starter is
stopped.
Verify that the motor FLA (QST 01) and CT ratio (FUN 03) settings are correct.
F46
Disconnect Open
A signal on the disconnect digital input (I/O 01 - I/O 08) was not present when a
start was commanded.
Verify that disconnect feedback wiring is correct.
Verify that disconnect is not faulty.
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...