FUN 04
P77
Phase Order
Input Phase Sensitivity
Insensitive
ABC
CBA
Single Phase
Insens.
102
FUN 05
P76
Rated Volts
Rated RMS Voltage
100, 110, 120, 200, 208,
220, 230, 240, 350, 380,
400, 415, 440, 460, 480,
500, 525, 575, 600, 660,
690, 1000, 1140, 2200,
2300, 2400, 3300, 4160,
4600, 4800, 6000, 6600,
6900, 10000, 11000,
11500, 12000, 12470,
13200, 13800
RMS
Voltage
480
103
FUN 06
P75
Motor PF
Motor Rated Power
Factor
-0.01 (Lag) to 1.00 (Unity)
-0.92
103
FUN 07
P74
Starter Type
Starter Type
Normal
Inside Delta
Wye-Delta
Phase Ctl
Curr Follow
ATL
Normal
103
FUN 08
P73
Heater Level
Heater Level
Off, 1 to 40
%FLA
Off
104
FUN 09
P72
Energy Saver
Energy Saver
Off, On
Seconds
Off
105
FUN 10
PORT Flt Tim
P.O.R.T. Fault Time
Off, 0.1 - 90.0
Seconds
Off
105
FUN 11
PORT Byp Tim
P.O.R.T. Bypass Hold
Time
Off, 0.1 - 5.0
Seconds
Off
105
FUN 12
PORT Recover
P.O.R.T. Recovery
Method
Voltage Ramp
Fast Recover
Current Ramp
Curr Ramp 2
Ramp Select
Tach Ramp
Fast
Recover
106
FUN 13
Tach FS Lvl
Tachometer Full Speed
Voltage
1.00 - 10.00
Volts
5.00
106
FUN 14
Tach Los Tim
Tachometer Loss Time
0.1 - 90.0
Seconds
1.5
106
FUN 15
Tach Los Act
Tachometer Loss Action
Fault
Current
TruTorque
KW
Fault
106
FUN 16
P70
Com Drop #
Communication Address
1 to 247
1
107
FUN 17
P69
Com Baud rate
Communication Baud
Rate
1200
2400
4800
9600
19200
bps
19200
107
FUN 18
P68
Com Timeout
Communication
Timeout
Off, 1 to 120
Seconds
Off
107
FUN 19
P71
Com Parity
Communications Byte
Framing
Even, 1 Stop Bit
Odd, 1 Stop Bit
None, 1 Stop Bit
None, 2 Stop Bit
Even, 1
Stop
108
FUN 20
P80
Software 1
Software Part Number 1
Display Only
108
FUN 21
Software 2
Software Part Number 2
Display Only
108
FUN 22
P67
Misc Command
Miscellaneous
Commands
None
Reset RT
Reset kWh
Reflash Mode
Store Parameters
Load Parameters
Factory Reset
Std BIST
Powered BIST
None
108
209
APPENDIX I - PARAMETER TABLES
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...