![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 33](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255033.webp)
Power Wiring
3.6
Power Wiring
Input Line Requirements
The input line source needs to be an adequate source to start the motor, generally 2 times the rating of the motor FLA. (This may not
apply in some cases such as being connected to a generator).
3.6.1
Recommended Wire Gauges
The wire gauge selection is based on the FLA of the motor. Refer to NEC table 310-16 or CEC Part 1, Table 2 or local code
requirements for selecting the correct wire sizing. Ensure appropriate wire derating for temperature is applied. If more than three current
carrying conductors are in one conduit, ensure NEC table 310.15(B)(2) or CEC Part 1 Table 5C is adhered to. In some areas local codes
may take precedence over the NEC. Refer to your local requirements.
3.6.2
Power Wire Connections
Attach the motor cables:
•
Use the T1, T2 and T3 terminals. Use lugs/crimps or terminals (lugs and crimps are to be provided by the user).
Attach the power source cables:
•
Use the L1, L2 and L3 terminals. Use lugs/crimps or terminals (lugs and crimps are to be provided by the user).
3.6.3
Motor Lead Length
The standard starter can operate a motor with a maximum of 600 feet of properly sized cable between the “T” leads of the starter and that
of the motor. For wire runs greater than 600 feet contact Benshaw Inc. for application assistance. If shielded cable is used, consult
factory for recommended length.
3.6.4
Compression Lugs
The following is a list of the recommended crimp-on wire connectors manufactured by Penn-Union Corp. for copper wire.
23
3 - INSTALLATION
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0S20
500 MCM
BLU-050S2
2/0
BLU-2/0S4
600 MCM
BLU-060S1
3/0
BLU-3/0S1
650 MCM
BLU-065S5
4/0
BLU-4/0S1
750 MCM
BLU-075S
250 MCM
BLU-025S
800 MCM
BLU-080S
300 MCM
BLU-030S
1000 MCM
BLU-100S
350 MCM
BLU-035S
1500 MCM
BLU-150S
400 MCM
BLU-040S4
2000 MCM
BLU-200s
450 MCM
BLU-045S1
Table 8: Single Hole Compression Lugs
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0D20
500 MCM
BLU-050D2
2/0
BLU-2/0D4
600 MCM
BLU-060D1
3/0
BLU-3/0D1
650 MCM
BLU-065D5
4/0
BLU-4/0D1
750 MCM
BLU-075D
250 MCM
BLU-025D
800 MCM
BLU-080D
300 MCM
BLU-030D
1000 MCM
BLU-100D
350 MCM
BLU-035D
1500 MCM
BLU-150D
400 MCM
BLU-040D4
2000 MCM
BLU-200D
450 MCM
BLU-045D1
Table 9: Two Hole Compression Lugs
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...