The correct installation of the current transformer on the motor leads is important. The shield ground wire should also be passed through
the CT window if the motor conductors use shielded cable. Otherwise, capacitive coupling of the phase current into the cable shield may
be measured as ground fault current. See Figure 8 below for proper installation.
z
NOTE:
Power cable must be covered with voltage rated sleeving/tubing extending a minimum of 8" past both sides of the CT.
26
3 - INSTALLATION
GROUND ON STARTER
POWER CABLE
TO MOTOR
GROUND WIRE DOES
NOT PASS THROUGH CT
CORE BALANCE
CT SECONDARY
CONNECTION TO
J15 ON MX
³
CARD
LUGS TO LOAD
TERMINALS ON
STARTER
50:0.025 CORE
BALANCE CT
Figure 8: Zero Sequence CT Installation Using Unshielded Cable
GROUND ON STARTER
POWER CABLE
TO MOTOR
GROUND WIRE MUST
PASS THROUGH CT
WINDOW
CORE BALANCE
CT SECONDARY
CONNECTION TO
J15 ON MX
³
CARD
LUGS TO LOAD
TERMINALS ON
STARTER
50:0.025 CORE
BALANCE CT
STRESS CONES
GROUND
Figure 9: Zero Sequence CT Installation Using Shielded Cable
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...