8 - TROUBLESHOOTING & MAINTENANCE
8.4.7
Metering incorrect
Condition
Cause
Solution
Power Metering not reading correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.
CT1=L1 CT2=L2 CT3=L3
CT ratio parameter (FUN03) set
incorrectly.
Verify that the CT ratio parameter is set
correctly.
PF Meter not reading correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.
Motor Current or Voltage meters
fluctuating with steady load.
Energy Saver active.
Turn off Energy Saver if not desired.
Loose connections.
Shut off all power and check all
connections.
SCR fault.
Verify that the SCRs gate leads are
connected properly and the SCRs are
ok.
Load actually is not steady.
Verify that the load is actually steady
and that there are not mechanical issues.
Other equipment on same power feed
causing power fluctuations and/or
distortion.
Fix cause of power fluctuations and/or
distortion.
Voltage Metering not reading correctly.
In medium voltage systems, Rated
Voltage parameter (FUN05) set
incorrectly.
Verify that Rated Voltage parameter is
set correctly.
Current Metering not reading correctly.
CT ratio parameter (FUN03) set
incorrectly.
Verify that the CT ratio (FUN03)
parameter is set correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.CT1=L1
CT2=L2 CT3=L3
Residual Ground Fault Current Metering
not reading correctly.
CT ratio parameter (FUN03) set
incorrectly.
Verify that the CT ratio parameter is set
correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.CT1=L1
CT2=L2 CT3=L3
Zero Sequence GF Metering not reading
correctly.
CT installed or wired incorrectly.
Verify CT installation.
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...