APPENDIX F - MODBUS REGISTER MAP
Absolute Register Address
Description
Range
Units
30199/40199
Misc. Commands
0:
None
1:
Reset Run Time
2:
Reset kWh
3:
Enter Reflash Mode
4:
Store Parameters
5:
Load Parameters
6:
Factory Reset
7:
Standard BIST
8:
Powered BIST
–
30221/40221
Acceleration Profile
0:
Linear
1:
Squared
2:
S-Curve
–
30222/40222
Deceleration Profile
–
30223/40223
PORT Bypass Enable
0:
Disabled
1:
Enabled
–
30224/40224
PORT Bypass Delay Time
1 – 50
100 mSec
30225/40225
PORT Recovery Method
0:
Voltage Ramp
1:
Fast Recover
2:
Current Ramp
3:
Current Ramp 2
4:
Ramp Select
5:
Tach Ramp
–
30226/40226
Tachometer Full Speed Voltage
100 – 1000
10 mV
30227/40227
Tachometer Loss Delay Time
1 – 900
100 mSec
30228/40228
Tachometer Loss Action
0: Fault
1: Closed Loop Current Ramp
2: TruTorque Ramp
3: Power Ramp
–
30229/40229
Time/Date Format
0: MM/DD/YY, 12 Hour
1: MM/DD/YY, 24 Hour
2: YY/MM/DD, 12 Hour
3: YY/MM/DD, 24 Hour
4: DD/MM/YY, 12 Hour
5: DD/MM/YY, 24 Hour
–
30230/40230
Current Imbalance Delay Time
1 – 900
100 mSec
30231/40231
Zero Sequence Ground Fault Trip Enable
0:
Disabled
1:
Enabled
–
30232/40232
Zero Sequence Ground Fault Trip Level
10 – 250
100 mArms
30233/40233
Ground Fault Delay Time
1 – 900
100 mSec
30234/40234
Phase Loss Delay Time
1 – 50
100 mSec
30235/40235
Over Frequency Trip Level
24 – 72
Hz
30236/40236
Under Frequency Trip Level
23 – 71
Hz
30237/40237
Over/Under Frequency Delay Time
1 – 900
100 mSec
30238/40238
Power Factor Leading Trip Enable
0:
Disabled
1:
Enabled
–
30239/40239
Power Factor Leading Trip Level
80 – 99 =-0.80 to -0.99 lag
100 – 120 =-1.00 to +0.80 lead
–
30240/40240
Power Factor Lagging Trip Enable
0:
Disabled
1:
Enabled
–
30241/40241
Power Factor Lagging Trip Level
1 – 99 = -0.01 to -0.99 lag
100 – 120 =1.00 to +0.80 lead
–
30242/40242
Power Factor Delay Time
1 – 900
100 mSec
30243/40243
Backspin Timer Enable
0:
Disabled
1:
Enabled
–
30244/40244
Backspin Time
1 – 180
Min
30245/40245
Time Between Starts Enable
0:
Disabled
1:
Enabled
–
30246/40246
Time Between Starts
1 – 180
Min
30247/40247
Starts per Hour Enable
0:
Disabled
1:
Enabled
–
30248/40248
Starts per Hour
1 – 6
–
30249/40249
Speed Switch Enable
0:
Disabled
1:
Enabled
–
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...