3.2.5
Use of Power Factor Capacitors
Power factor correction capacitors and surge capacitors CAN NOT be connected between the starter and the motor. These devices can
damage the SCRs during ramping. These devices appear like a short circuit to the SCR when it turns on, which causes a di/dt level
greater than the SCR can handle. If used, power factor correction capacitors or surge capacitors must be connected ahead of the starter
and sequenced into the power circuit after the start is completed. A programmable relay can be configured as an up-to-speed (UTS) relay
and then used to pull-in a contactor to connect the capacitors after the motor has reached full speed.
z
NOTE:
If the motor manufacturer supplies surge capacitors they must be removed before starting.
20
3 - INSTALLATION
Figure 4: Separate Power Factor Correction Disconnect
Figure 5: Integral Power Factor Correction Disconnect
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...