![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 116](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255116.webp)
P.O.R.T. Recovery Method
FUN 12
LCD Display
Range
LCD
Description
Fast Recover
Current acceleration ramp from 100% FLA -> 800% FLA with a
ramp time of 1 second.
(Default)
Current Ramp
Current acceleration ramp using the Ramp#1 user parameter settings.
Current Ramp 2
Current acceleration ramp using the Ramp#2 user parameter settings.
Ramp Select
Current acceleration ramp using the appropriate current ramp
selected by the RAMP Select digital input.
Tach Ramp
Speed controlled acceleration ramp. Ramp starts at motor speed
measured at start of recovery and accelerates motor at same slope
(acceleration rate) as a normal tachometer start from zero speed
would do.
Description
The PORT Recovery parameter sets how the starter will re-accelerate the motor when power returns.
Tachometer Full Speed Voltage
FUN 13
LCD Display
Range
1.00 – 10.00 V in 0.01 volt increments
(Default: 5.00V)
Description
The Tachometer Full Speed Voltage parameter sets the tachometer input voltage at full speed. This value
should be set at full (unloaded) motor speed.
Ex. A tachometer rated at 0.0033 volts-per-rpm is mounted on a 4-pole 1800 rpm motor. Therefore, the FS
Volts should be set to: 0.0033 * 1800 = 5.94 volts.
Tachometer Loss Time
FUN 14
LCD Display
Range
0.1 – 90.0 seconds
(Default: 1.5)
Description
The Tachometer Loss Time is the allowable time the starter will operate when a tachometer signal is lost. If
the signal is lost, the starter will perform the action set by the Tach Loss Action parameter.
z
NOTE:
Nuisance tachometer loss faults at start can be prevented by setting the initial current parameter to
a value that allows the motor to begin rotating soon after a start is commanded.
Tachometer Loss Action
FUN 15
LCD Display
Range
LCD
Description
Fault
The starter will shutdown and indicate a tachometer loss fault.
Current Acceleration
If the tachometer signal is lost the starter will fault. However the start mode
parameter will be set to Current control acceleration so that when the fault is
reset the starter will start in current control mode.
106
6 - PARAMETER DESCRIPTION
FUN: Tach FS Lvl
13
5.00 Vlt
FUN: Tach Los Tim
14
1.5
sec
FUN: Tach Los Act
15
Fault
FUN: PORT Recover
12
Fast Recover
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...