If the keypad is selected as local or remote control sources, the [STOP] key cannot be disabled.
If “Enabled”
When this parameter is set to "Enabled", the keypad stop button is enabled and stops the starter regardless of
the selected control source (keypad, terminal or serial).
See Also
Local Source parameter (QST 04) on page 59.
Remote Source parameter (QST 05) on page 60.
Auto Start Selection
I/O 27
LCD Display
Range
LCD
Description
Disabled
When Disabled, the Start input must always transition from low to high
for a start to occur.
(Default)
Power
When set to Power, a start will occur if the Start input is high while
control power is applied.
Fault
When set to Fault, a start will occur if the Start input is high when a
fault is reset.
Power, Fault
When set to Power and Fault, a start will occur if the Start input is
high while control power is applied, and a start will occur if the Start
input is high when a fault is reset.
Description
The Auto Start Selection parameter determines whether or not a transition from low to high is required on the
Start input for a start to occur after either a power up or a fault reset. This applies to lockout conditions being
cleared as well. The behavior for a lockout clearing is the same as for a fault being reset.
Jump to Parameter
RTD 00
LCD Display
Description
By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter
within that group.
RTD Module #1 Address
RTD 01
LCD Display
Range
Off, 16 to 23
(Default Off)
Description
The module #1 address parameter has to be set to the Modbus address of the first RTD module attached to the
soft-starter. The address of the RTD module can be verified by checking the rotary switch on the top of the
RTD module.
97
6 - PARAMETER DESCRIPTION
I/O: Auto Start
27 Disabled
RTD: Jump Code
00
1
RTD: RTDMod1 Addr
01
Off
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...