Analog Input Offset parameter (I/O 20) on page 94.
Starter Type parameter (FUN 07) on page 103.
Analog Input Offset
I/O 20
LCD Display
Range
0 – 99 %
(Default: 0)
Description
The analog input can be offset so that a 0 % reading can occur when a non-zero input signal is being applied.
Example: Input level of 2V (4mA) => 0% input. In this case the Analog Input Offset parameter should be set
to 20 % so that the 2V (4mA) input signal results in a 0 % input reading.
z
NOTE:
For a 4-20mA input, set the Analog Input Span to 80 % and the Analog Input Offset to 20 %.
z
NOTE:
The measured input reading is clamped at 0 % minimum.
See Also
Analog Input Trip Level parameter (I/O 17) on page 92.
Analog Input Trip Time parameter (I/O 18) on page 93.
Analog Input Span parameter (I/O 19) on page 93.
Starter Type parameter (FUN 07) on page 103.
Analog Output Function
I/O 21
LCD Display
Range
LCD
Description
Off
Off, Disabled
(Default
)
0 – 200% Curr
Based on per cycle RMS values
0 – 800% Curr
Based on per cycle RMS values
0 – 150% Volt
Based on per cycle RMS values
0 – 150% OL
Motor Thermal Overload
0 – 10 kW
Based on filtered V and I values
0 – 100 kW
Based on filtered V and I values
0 – 1 MW
Based on filtered V and I values
0 – 10 MW
Based on filtered V and I values
0 – 100% Ain
The output value takes into account the inputs span and offset settings
0 – 100% Firing
Output Voltage to Motor, based on SCR firing angle
Calibration
Calibration, full (100%) output
Description
The Analog Output Function parameter selects the function of the analog output. The available analog output
function selections and output scaling are shown below. The analog output is updated every 25msec.
See Also
Analog Output Span parameter (I/O 22) on page 95.
Analog Output Offset parameter (I/O 23) on page 95.
94
6 - PARAMETER DESCRIPTION
I/O: Aout Fctn
21
Off
I/O: Ain Offset
20
0 %
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...