![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 25](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255025.webp)
Environmental Conditions
2.4
Environmental Conditions
Altitude Derating
2.5
Altitude Derating
Benshaw's starters are capable of operating at altitudes up to 3,300 feet (1000 meters) without requiring altitude derating. Table 6
provides the derating percentage to be considered when using a starter above 3,300 feet (1000 meters).
Real Time Clock
2.6
Real Time Clock
The MX
3
comes with a real time clock. The user can enter the actual time and the starter will use this time when it logs faults in the fault
recorder as well as events in the event recorder. This can help with troubleshooting. The system clock does not recognize daylight
savings time.
Accuracy: +- 1 minute per month
Range: 1/1/1972 to 1/1/2107 with automatic leap year compensation.
Approvals
2.7
Approvals
MX
3
Control Card Set is UL, cUL Recognized
Certificate of Compliance
2.8
Certificate of Compliance
CE Mark, see Appendix E on page 184.
15
2 - TECHNICAL SPECIFICATIONS
Altitude
Percent Derating (Amps)
3300 Feet
1006 meters
0.0%
4300 Feet
1311 meters
3.0%
5300 Feet
1615 meters
6.0%
6300 Feet
1920 meters
9.0%
7300 Feet
2225 meters
12.0%
8300 Feet
2530 meters
15.0%
9300 Feet
2835 meters
18.0%
For derating above 10,000 feet consult Benshaw Inc.
Table 6: Altitude Derating
Operating Temperatures
-10°C to +40°C (14°F to 104°F)enclosed
-10°C to +50°C (14°F to 122°F)open
Storage Temperatures
-20°C to +70°C (-4°F to 155°F)
Humidity
0% to 95% non condensing
Altitude
1000m (3300ft) without derating
Maximum Vibration
5.9m/s
2
(19.2ft/s
2
) [0.6G]
Cooling
Natural convection
(Fans optional)
Table 7: Environmental Ratings
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...