![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 216](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255216.webp)
Group
LED
Display
Parameter
Setting Range
Units
Default
Page
Setting
PFN 31
P46
OL H/C Ratio
Motor Overload Hot/Cold Ratio
0 - 99
%
60
88
PFN 32
P47
OL Cool Time
Motor Overload Cooling Time
1.0 - 999.9
Minutes
30
88
PFN 33
OL Alarm Lvl
Motor OL Alarm Level
1 - 100
%
90
89
PFN 34
OL Lock Lvl
Motor OL Lockout Level
1 - 99
%
15
89
PFN 35
OL Lock Calc
Motor OL Auto Lockout Level
Off, Auto
Off
89
I/O Group
Group
LED
Display
Parameter
Setting Range
Units
Default
Page
Setting
I/O 00
Jump Code
Jump to parameter
1 to 27
1
90
I/O 01
P48
DI 1 Config
Digital Input #1
Configuration
Off
Heat Disable
Stop
Heat Enable
Fault High
Ramp Select
Fault Low
Slow Spd Fwd
Fault Reset
Slow Spd Rev
Disconnect
Brake Disable
Inline Cnfrm
Brake Enable
Bypass Cnfrm
Speed Sw NO
E OL Reset
Speed Sw NC
Local/Remote
Stop
90
I/O 02
P49
DI 2 Config
Digital Input #2
Configuration
Off
I/O 03
P50
DI 3 Config
Digital Input #3
Configuration
Off
I/O 04
DI 4 Config
Digital Input #4
Configuration
Off
I/O 05
DI 5 Config
Digital Input #5
Configuration
Off
I/O 06
DI 6 Config
Digital Input #6
Configuration
Off
I/O 07
DI 7 Config
Digital Input #7
Configuration
Off
I/O 08
DI 8 Config
Digital Input #8
Configuration
Off
I/O 09
P51
Dig Trp Time
Digital Fault Input Trip Time
0.1 to 90.0
Seconds
0.1
91
I/O 10
P52
R1 Config
Relay Output
#1Configuration
Off
Ground Fault
Fault FS
Energy Saver
Fault NFS
Heating
Running
Slow Spd
UTS
Slow Spd Fwd
Alarm
Slow Spd Rev
Ready
Braking
Locked Out
Cool Fan Ctl
Overcurrent
PORT
Undercurrent
Tach Loss
OL Alarm
Shunt FS
Shunt NFS
Fault FS
91
I/O 11
P53
R2 Config
Relay Output #2
Configuration
Off
I/O 12
P54
R3 Config
Relay Output #3
Configuration
Off
I/O 13
R4 Config
Relay Output #4
Configuration
Off
I/O 14
R5 Config
Relay Output #5
Configuration
Off
I/O 15
R6 Config
Relay Output #6
Configuration
Off
I/O 16
P55
Ain Trp Type
Analog Input Trip Type
Off
Low Level
High Level
Off
92
I/O 17
P56
Ain Trp Lvl
Analog Input Trip Level
0 to 100
%
50
92
I/O 18
P57
Ain Trp Tim
Analog Input Trip Delay
Time
0.1 to 90.0
Seconds
0.1
93
I/O 19
P58
Ain Span
Analog Input Span
1 to 100
%
100
93
I/O 20
P59
Ain Offset
Analog Input Offset
0 to 99
%
0
94
206
APPENDIX I - PARAMETER TABLES
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...