Parameter Table
Following is the parameter table for both the LED and LCD Display. The last column is a convenient place to write down parameter
settings.
Quick Start Group
Control Function Group
Group
LED
Display
Parameter
Setting Range
Units
Default
Page
Setting
CFN 00
Jump Code
Jump to Parameter
1 to 25
1
63
CFN 01
P10
Start Mode
Start Mode
Voltage Ramp
Current Ramp
TT Ramp
Power Ramp
Tach Ramp
Current Ramp
63
CFN 02
P8
Ramp Time 1
Ramp Time 1
0 to 300
Seconds
15
64
CFN 03
P6
Init Cur 1
Initial Motor Current 1
50 to 600
%FLA
100
64
CFN 04
P7
Max Cur 1
Maximum Motor Current 1
100 to 800
%FLA
600
65
CFN 05
P24
Ramp Time 2
Ramp Time 2
0 to 300
Seconds
15
65
CFN 06
P22
Init Cur 2
Initial Motor Current 2
50 to 600
%FLA
100
65
CFN 07
P23
Max Cur 2
Maximum Motor Current 2
100 to 800
%FLA
600
66
CFN 08
P11
Init V/T/P
Initial Voltage/Torque/Power
1 to 100
%
25
66
CFN 09
P12
Max T/P
Maximum Torque/Power
10 to 325
%
105
67
CFN 10
Accel Prof
Acceleration Ramp Profile
Linear
Squared
S-Curve
Linear
67
CFN 11
P13
Kick Lvl 1
Kick Level 1
Off, 100 to 800
%FLA
Off
68
CFN 12
P14
Kick Time 1
Kick Time 1
0.1 to 10.0
Seconds
1.0
69
CFN 13
P25
Kick Lvl 2
Kick Level 2
Off, 100 to 800
%FLA
Off
69
CFN 14
P26
Kick Time 2
Kick Time 2
0.1 to 10.0
Seconds
1.0
69
CFN 15
P15
Stop Mode
Stop Mode
Coast
Volt Decel
TT Decel
DC Brake
Coast
70
CFN 16
P16
Decel Begin
Decel Begin Level
100 to 1
%
40
70
CFN 17
P17
Decel End
Decel End Level
99 to 1
%
20
71
CFN 18
P18
Decel Time
Decel Time
1 to 180
Seconds
15
71
CFN 19
Decel Prof
Decel Ramp
Profile
Linear
Squared
S-Curve
Linear
72
CFN 20
P19
Brake Level
DC Brake Level
10 to 100
%
25
72
CFN 21
P20
Brake Time
DC Brake Time
1 to 180
Seconds
5
73
204
APPENDIX I - PARAMETER TABLES
LED
LCD
Display
Parameter
Setting Range
Units
Default
Page
Setting
P1
QST 01
Motor FLA
Motor FLA
1 – 6400
RMS Amps
10
58
P2
QST 02
Motor SF
Motor Service Factor
1.00 – 1.99
1.15
58
P3
QST 03
Running OL
Motor Running Overload Class
Off, 1 – 40
10
59
P4
QST 04
Local Src
Local Source
Keypad
Terminal
Serial
Terminal
59
P5
QST 05
Remote Src
Remote Source
60
P6
QST 06
Init Cur 1
Initial Motor Current 1
50 – 600
%FLA
100
61
P7
QST 07
Max Cur 1
Maximum Motor Current 1
100 – 800
%FLA
600
61
P8
QST 08
Ramp Time 1
Ramp Time 1
0 – 300
Seconds
15
62
P9
QST 09
UTS Time
UTS Time / Transition Time
1 – 900
Seconds
20
62
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...