![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 22](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255022.webp)
2.2.5
CT Ratios
2.2.6
Optional RTD Module Specifications
The starter has the option of operating with up to two Benshaw SPR-100P remote RTD modules.
12
2 - TECHNICAL SPECIFICATIONS
CT Ratio (x:5)
Minimum FLA
(A rms)
Maximum FLA
(A rms)
50:5
11
45
150:5
33
135
250:5
55
225
800:5
176
720
2000:5
440
1800
5000:5
1100
4500
Table 3: CT Ratios
Model Number
SPR-100P
RTD Type
100
W
Platinum, 3 lead
TCR (
a
)
0.00385
W
/
W
/
°
C
(DIN 43760)
Maximum Lead Resistance
25
W
per lead
Recommended Lead Resistance
Less than 16
W
per lead
Shorted Lead Detection
< 60
W
Open Lead Detection
> 260
W
RTD Sensing Current
10 mA DC
RTD Sensing Voltage
10V DC maximum
Range
0 to 200
°
C (32 to 392
°
F)
Resolution
1
°
C (1.8
°
F)
Accuracy
±
1.0% full scale (
±
2
°
C or
±
3.6
°
F)
Sampling Rate
1 RTD per second
Number of RTDs
8
Input Voltage
24 Volts DC
±
20%, 2.5W
Communication Type
Modbus RTU, RS-485, 19.2Kbps
Modbus
®
Addresses
16 to 23
Operating Environment
-40 to 60
°
C (-40 to 140
°
F), up to 95% R.H., non-condensing
Terminal Strips
Accepts one or two stranded copper wires of the same size
from 12 to 30 AWG
Dimensions
5 ½" W x 3 ½" H x 2 ¼" D
Listing
cUL
Table 4: Remote RTD Module Specifications
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...