91
6 - PARAMETER DESCRIPTION
See Also
Local Source parameter (QST 04) on page 59.
Remote Source parameter (QST 05) on page 60.
Bypass Feedback Time parameter (I/O 25) on page 96.
Heater Level parameter (FUN 08) on page 104.
Theory of Operation section 7.1.12, Emergency Motor Overload Reset on page 121.
Theory of Operation section 7.3.6, Dual Acceleration Ramp Control on page 128.
Theory of Operation section 7.6.2, Wye-Delta Operation on page 139.
Theory of Operation section 7.8, Start/Stop Control with a Hand/Off/Auto Selector Switch on page 141.
Digital Fault Input Trip Time
I/O 09
LCD Display
Range
0.1 – 90.0 Seconds
(Default: 0.1 Sec)
Description:
The Digital Fault Input Trip Time parameter sets the length of time the digital input must be high or low
before a trip occurs. This delay time only functions for fault high and fault low.
See Also
Digital Input Configuration parameter on page 90.
Relay Output Configuration
I/O 10 - 15
LCD Display
Range
LCD
Description
Off
Off, Not Assigned. May be controlled over Modbus
(Default: R - 2, 3, 4, 5, 6)
Fault FS
Faulted – Fail Safe operation. Energized when no faults present, de-energized when
faulted.
(Default: R1)
Fault NFS
Faulted– Non Fail Safe operation. Energized when faulted.
Running
Running, starter running, voltage applied to motor.
UTS
Up to Speed, motor up to speed or transition to for Wye/Delta Operation.
Alarm
Alarm, any alarm condition present.
Ready
Ready, starter ready for start command.
Locked Out
Locked Out.
OverCurrent
Over Current Alarm, over current condition detected.
UnderCurrent
Under Current Alarm, under current condition detected.
OL Alarm
Overload Alarm.
Shunt FS
Shunt Trip Relay – Fail Safe operation, energized when no shunt trip, fault present,
de-energized on shunt trip fault.
Shunt NFS
Shunt Trip Relay – Non Fail Safe operation, de-energized when no shunt trip fault
present, energized on shunt trip fault.
Ground Fault
A Ground Fault trip has occurred.
Energy Saver
Operating in Energy Saver Mode.
Heating
Motor Heating, starter applying heating pulses to motor.
Slow Spd
Starter operating in slow speed mode.
Slow Spd Fwd
Starter operating in slow speed forward mode.
Slow Spd Rev
Starter operating in slow speed reverse mode.
Braking
Starter is applying DC brake current to motor.
Cool Fan Ctl
Heatsink fan control.
PORT
Energized when the starter is in the Power Outage Ride Through mode.
Tach Loss
Energized when the starter has faulted on a Tachometer Loss of Signal Fault.
I/O: R5 Config
14
Off
I/O: R6 Config
15
Off
I/O: R4 Config
13
Off
I/O: R1 Config
10 Fault FS
I/O: R2 Config
11
Off
I/O: R3 Config
12
Off
I/O: Din Trp Time
09
0.1 sec
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...