Safety Precautions
8.1
Safety Precautions
For safety of maintenance personal as well as others who might be exposed to electrical hazards associated with maintenance activities,
the safety related work practices of NFPA 70E, Part II, should always be followed when working on electrical equipment. Maintenance
personnel must be trained in the safety practices, procedures, and requirements that pertain to their respective job assignments.
WARNING:
To avoid shock hazard, disconnect main before working on controller/starter, motor or control devices such as start/stop
pushbuttons. Procedures which require parts of the equipment to be energized during troubleshooting, testing, etc, must be performed by
properly qualified personnel, using appropriate work practices and precautionary measures as specified in NFPA70, Part II.
CAUTION:
Disconnect the controller/starter from the motor before measuring insulation resistance (IR) or the motor windings.
Voltages used for insulation resistance testing can cause failure of SCR's. Do not make any measurements on the controller with an IR
tester (megger).
z
NOTE:
Blades against ground bar.
Preventative Maintenance
8.2
Preventative Maintenance
8.2.1
General Information
Preventative maintenance performed on a regular basis will help ensure that the starter continues to operate reliably and safely. The
frequency of preventative maintenance depends upon the type of maintenance and the installation site’s environment.
z
NOTE:
A trained technician should always perform preventative maintenance.
8.2.2
Preventative Maintenance
During Commissioning:
•
Torque all power connections during commissioning. This includes factory wired equipment.
•
Check all of the control wiring in the package for loose connections.
•
If fans are installed, ensure proper operation
One month after the starter has been put in operation:
•
Re-torque all power connections during the month. This includes factory wired equipment.
•
Inspect the cooling fans after two weeks to ensure proper operation.
After the first month of operation:
•
Re-torque all power connections every year.
•
Clean any accumulated dust from the starter using a clean source of compressed air or a vacuum cleaner.
•
Inspect the cooling fans every three months to ensure proper operation.
•
Clean or replace any air vent filters on the starter every three months.
z
NOTE:
If mechanical vibrations are present at the installation site, inspect the electrical connections more frequently.
148
8 - TROUBLESHOOTING & MAINTENANCE
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...