6 - PARAMETER DESCRIPTION
TruTorque Accel
If the tachometer signal is lost the starter will fault. However the start mode
parameter will be set to TruTorque control acceleration so that when the fault is
reset the starter will start in Current control mode.
KW (Power)
If the tachometer signal is lost the starter will fault. However the start mode
parameter will be set to KW (Power) so that when the fault is reset the starter
will start in Current control mode.
Description
If the tachometer detects the feedback signal is not valid one of the above actions will be taken depending on
the value of the Tach Loss Action user parameter.
Communication Address
FUN 16
LCD Display
Range
1 – 247
(Default: 1)
Description
The Communication Address parameter sets the starter’s address for Modbus communications.
See Also
Local Source parameter (QST 04) on page 59.
Remote Source parameter (QST 05) on page 60.
Communication Baud Rate parameter (FUN 17) on page 107.
Communication Timeout parameter (FUN 18) on page 107.
Communication Byte Framing parameter (FUN 19) on page 108.
Communication Baud Rate
FUN 17
LCD Display
Range
1200, 2400, 4800, 9600, 19200 bps
(Default: 19200)
Description
The Communication Baud Rate parameter sets the baud rate for Modbus communications.
See Also
Local Source parameter (QST 04) on page 59.
Remote Source parameter (QST 05) on page 60.
Communication Address parameter (FUN 16) on page 107.
Communication Timeout parameter (FUN 18) on page 107.
Communication Byte Framing parameter (FUN 19) on page 108.
Communication Timeout
FUN 18
LCD Display
Range
Off, 1 – 120 seconds
(Default: Off)
Description
The Communication Timeout parameter sets the time that the starter continues to run without receiving a valid
Modbus request. If a valid Modbus request is not received for the time that is set, the starter declares an F82
(Modbus Time Out). The starter performs a controlled stop.
See Also
Local Source parameter (QST 04) on page 59.
Remote Source parameter (QST 05) on page 60.
Stop Mode parameter (CFN 15) on page 70.
Controlled Fault Stop Enable parameter (PFN 25) on page 85.
Communication Address parameter (FUN 16) on page 107.
Communication Baud Rate parameter (FUN 17) on page 107.
FUN: Com Drop #
16
1
FUN: Com Baudrate
17
19200
FUN: Com Timeout
18
Off
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...