APPENDIX F - MODBUS REGISTER MAP
Absolute Register Address
Description
Range
Units
30058/40058
Peak Starting Current
A
rms
30059/40059
Last Starting Duration
0.1 Sec
30060/40060
Hottest Stator RTD Temperature
0 - 200
°
C
30061/40061
Hottest Bearing RTD Temperature
0 - 200
°
C
30062/40062
Hottest Other RTD Temperature
0 - 200
°
C
30063/40063
RTD 1 Temperature
0 - 200
°
C
30064/40064
RTD 2 Temperature
0 - 200
°
C
30065/30065
RTD 3 Temperature
0 - 200
°
C
30066/40066
RTD 4 Temperature
0 - 200
°
C
30067/40067
RTD 5 Temperature
0 - 200
°
C
30068/40068
RTD 6 Temperature
0 - 200
°
C
30069/40069
RTD 7 Temperature
0 - 200
°
C
30070/40070
RTD 8 Temperature
0 - 200
°
C
30071/40071
RTD 9 Temperature
0 - 200
°
C
30072/40072
RTD 10 Temperature
0 - 200
°
C
30073/40073
RTD 11 Temperature
0 - 200
°
C
30074/40074
RTD 12 Temperature
0 - 200
°
C
30075/40075
RTD 13 Temperature
0 - 200
°
C
30076/40076
RTD 14 Temperature
0 - 200
°
C
30077/40077
RTD 15 Temperature
0 - 200
°
C
30078/40078
RTD 16 Temperature
0 - 200
°
C
30079/40079
RTDs Enabled
Bit Mask:
Each of the sixteen (16) bits represents an
RTD. A 1 indicates the RTD is enabled.
Bit 0 represents RTD 1. Bit 15 represents
RTD 16.
–
30080/40080
RTDs Assigned as Stator
Bit Mask:
Each of the sixteen (16) bits represents an
RTD. A 1 indicates the RTD is assigned to
the stator group.
–
30081/40081
RTDs Assigned as Bearing
Bit Mask:
Each of the sixteen (16) bits represents an
RTD. A 1 indicates the RTD is assigned to
the bearing group.
–
30082/40082
RTDs Assigned as Other
Bit Mask:
Each of the sixteen (16) bits represents an
RTD. A 1 indicates the RTD is assigned to
the other group.
–
30083/40083
RTDs with Open Leads
Bit Mask:
Each of the sixteen (16) bits represents an
RTD. A 1 indicates the RTD has an open
lead.
–
30084/40084
RTDs with Shorted Leads
Bit Mask:
Each of the sixteen (16) bits represents an
RTD. A 1 indicates the RTD has shorted
leads.
–
30085/40085
Remaining Lockout Time
Sec
30086/40086
Date/Time (lower 16 bits)
(in 32-bit unsigned integer format)
Sec
30087/40087
Date/Time (upper 16 bits)
30101/40101
Motor FLA
1 – 6400
A
rms
30102/40102
Motor Service Factor
100 – 199
0.01
30103/40103
Independent Start/Run Motor Overloads
0:
Disabled
1:
Enabled
–
30104/40104
Motor Overload Running Enable
0:
Disabled
1:
Enabled
–
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...