![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 196](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255196.webp)
186
APPENDIX F - MODBUS REGISTER MAP
Absolute Register Address
Description
Range
Units
30025/40025
Alarm Status 3
Bit 0:
“A 64” – DI 5
Bit 1:
“A 65” – DI 6
Bit 2:
“A 66” – DI 7
Bit 3:
“A 67” – DI 8
Bit 4:
“A 71” – Analog Input Trip
–
30026/40026
Lockout Status
Bit 0:
Motor overload
Bit 1:
Motor PTC
Bit 2:
RTD Stator
Bit 3:
RTD Bearing
Bit 4:
RTD Other
Bit 5:
Disconnect open
Bit 6:
Stack overtemperature
Bit 7:
Control power
Bit 8:
RTD Open/Short
Bit 9:
Time between starts
Bit 10:
Backspin
Bit 11:
Starts per hour
Bit 12:
RTD Comm Loss
–
30027/40027
Present Fault Code
30028/40028
Average Current
A
rms
30029/40029
L1 Current
A
rms
30030/40030
L2 Current
A
rms
30031/40031
L3 Current
A
rms
30032/40032
Current Imbalance
0.1 %
30033/40033
Residual Ground Fault Current
% FLA
30034/40034
Zero Sequence Ground Fault Current
0.1 Arms
30035/40035
Average Voltage
V
rms
30036/40036
L1-L2 Voltage
V
rms
30037/40037
L2-L3 Voltage
V
rms
30038/40038
L3-L1 Voltage
V
rms
30039/40039
Motor Overload
%
30040/40040
Power Factor
-99 to +100
(in 16-bit two’s compliment signed format)
0.01
30041/40041
Watts (lower 16 bits)
(in 32-bit unsigned integer format)
W
30042/40042
Watts (upper 16 bits)
30043/40043
VA (lower 16 bits)
(in 32-bit unsigned integer format)
VA
30044/40044
VA (upper 16 bits)
30045/40045
vars (lower 16 bits)
(in 32-bit two’s compliment signed integer
format)
var
30046/40046
vars (upper 16 bits)
30047/40047
kW hours (lower 16 bits)
(in 32-bit unsigned integer format)
kWh
30048/40048
kW hours (upper16 bits)
30049/40049
Phase Order
0:
no line
1:
ABC
2:
CBA
3:
SPH
–
30050/40050
Line Frequency
230 – 720, or 0 if no line
0.1 Hz
30051/40051
Analog Input %
-1000 to +1000
(in 16-bit two’s compliment signed format)
0.1 %
30052/40052
Analog Output %
0 – 1000
0.1 %
30053/40053
Running Time
0 – 65535
hours
30054/40054
Running Time
0 – 59
minutes
30055/40055
Starts
–
30056/40056
TruTorque %
%
30057/40057
Power %
%
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...