L2-L3 Volts
Voltage in, L2 to L3 RMS.
L3-L1 Volts
Voltage in, L3 to L1 RMS.
Overload
Thermal overload in %.
Power Factor
Motor power factor.
Watts
Motor real power consumed.
VA
Motor apparent power consumed.
vars
Motor reactive power consumed.
kW hours
Kilo-watt-hour used by the motor, wraps at 1,000.
MW hours
Mega-watt-hour used by the motor, wraps at 10,000.
Phase Order
Phase Rotation.
Line Freq
Line Frequency.
Analog In
Analog Input %.
Analog Out
Analog Output %.
Run Days
Running time in days, wraps at 2,730 days.
Run Hours
Running time in Hours and Minutes, wraps at 24:00.
Starts
Number of Starts, wraps at 65,536.
TruTorque %
TruTorque %.
Power %
Power %.
Pk accel Curr
Peak starting current.
Last Start T
Last starting duration.
Zero Seq GF
Zero sequence ground fault.
Stator Temp
Highest Stator temperature.
Bearing Temp
Highest Bearing temperature.
Other Temp
Highest Other temperature.
All Temp
Highest of all temperatures.
Description
Parameters FUN 01 and FUN 02 configure which meters are displayed on the two lines of the main display
screen.
CT Ratio
FUN 03
LCD Display
Range
72:1, 96:1, 144:1, 288:1, 864:1, 2640:1, 3900:1, 5760:1, 8000:1, 14400:1, 28800:1, 50:5, 150:5, 250:5, 800:5,
2000:5, 5000:5
(Default: 288:1)
Description
The CT Ratio parameter must be set to match the CTs (current transformers) supplied with the starter. This
allows the starter to properly calculate the current supplied to the motor.
z
NOTE:
It is very important that the CT ratio is set correctly. Otherwise, many starter functions will not
operate correctly.
Input Phase Sensitivity
FUN 04
LCD Display
Range
LCD
Description
Insensitive
Runs with any three phase sequence.
(Default)
ABC
Only runs with ABC phase sequence.
CBA
Only runs with CBA phase sequence.
Single phase
Single Phase.
Description
The Phase Order parameter sets the phase sensitivity of the starter. This can be used to protect the motor from
a possible change in the incoming phase sequence. If the incoming phase sequence does not match the set
phase rotation, the starter displays an alarm while stopped and faults if a start is attempted.
102
6 - PARAMETER DESCRIPTION
FUN:
CT Ratio
03
50:5
FUN: Phase Order
04
Insensitive
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...