![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 79](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255079.webp)
Kick Time 1
CFN 12
LCD Display
Range
0.1 – 10.0 seconds
(Default: 1.0 sec)
Description
The Kick Time 1 parameter sets the length of time that the kick current level is applied to the motor.
The kick time adjustment should begin at 0.5 seconds and be adjusted by 0.1 or 0.2 second intervals until the
motor begins rotating. If the kick time is adjusted above 2.0 seconds without the motor rotating, start over
with a higher kick current setting.
z
NOTE:
The kick time adds to the total start time and must be accounted for when setting the UTS time.
See Also
Up To Speed (QST 09) on page 62
Start Mode (CFN 01) on page 63.
Kick Level 1 (CFN 11) on page 68.
Theory of Operation section 7.3.2, Programming A Kick Current on page 124.
Kick Level 2
CFN 13
LCD Display
Range
Off, 100 – 800% of FLA
(Default: Off)
Description
The Kick Level 2 parameter sets the current level that precedes any ramp when a start is first commanded
when the second ramp is active. Refer to the Kick Level 1 (CFN 11) parameter on page 68 for description of
operation.
Kick Time 2
CFN 14
LCD Display
Range
0.1 – 10.0 seconds
(Default: 1.0 sec)
Description
The Kick Time 2 parameter sets the length of time that the kick current level is applied to the motor when the
second ramp is active. Refer to the Kick Time 1 (CFN 12) parameter on page 69 for description of operation.
See Also
Kick Level 1 (CFN 11) on page 68.
Digital Input Configuration (I/O 01 - 08) on page 90.
Theory of Operation section 7.3.2, Programming A Kick Current on page 124.
Theory of Operation section 7.3.6, Dual Acceleration Ramp Control on page 128.
69
6 - PARAMETER DESCRIPTION
CFN: Kick Lvl 2
13
Off
CFN: Kick Time 2
14
1.0 sec
CFN: Kick Time 1
12
1.0 sec
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...