APPENDIX F - MODBUS REGISTER MAP
Absolute Register Address
Description
Range
Units
30601/40601
to
30609/40609
Fault Code (newest fault)
to
Fault Code (oldest fault)
Refer to page 181
–
30611/40611
to
30619/40619
System States
:
The state that the starter
was in when the fault has occurred.
0:
Initializing
1:
Locked Out
2:
Faulted
3:
Stopped
4:
Heating
5:
Kicking
6:
Ramping
7:
Slow Speed
8:
Not UTS
9:
UTS (up to speed)
10: Phase Control / Current Follower
11: Decelling
12: Braking
13: Wye
14: PORT
15: BIST
16: Shorted SCR Test
17: Open SCR Test
–
30621/40621
to
30629/40629
L1 Currents: The current that the load is
drawing from Line 1 when the fault has
occurred.
Arms
30631/40631
to
30639/40639
L2 Currents: The current that the load is
drawing from Line 2 when a fault occurs.
Arms
30641.40649
to
30649/40649
L3 Currents: The current that the load is
drawing from Line 3 when a fault occurs.
Arms
30651/40651
to
30659/40659
L1 – L2 Voltages: The line voltage that is
present between lines 1 and 2 when a fault
occurs.
Vrms
30661/40661
to
30669/40669
L2 – L3 Voltages: The line voltage that is
present between lines 2 and 3 when a fault
occurs.
Vrms
30671/40671
to
30679/40679
L3 – L1 Voltages: The line voltage that is
present between lines 3 and 1 when a fault
occurs.
Vrms
30681/40681
to
30689/40689
Kilowatts: The power that the load is
drawing when a fault occurs.
KW
30691/40691
to
30699/40699
Line Periods: The line period
(1/frequency) that is present when a fault
occurs.
microseconds
30701/40701
to
30709/40709
Run Time Hours: The value of the
running time meter when a fault occurs.
Hours
30711/40711
to
30719/40719
Run Time Counts: The value of the
running time meter when a fault occurs.
The running counts provides more
resolution than the running time hours.
resets to 0 each time the running time
hours increments (at 35 999)
10 counts/sec
30801/40801 (newest)
to
30899/40899 (oldest)
Event Codes: Bit 15 indicates whether a
record is an event or fault. A 1 indicates
fault and a 0 indicates an event. The
remaining 15 bits contain the code.
refer to page 178
30901/40901 (newest)
to
30999/40999 (oldest)
The system state when the event or fault
occurred may be read.
refer to address 30611 – 30619
31001/41001
to
31198/41198
Time and Date Stamp
2 registers= 32 bit unsigned integer / event.
seconds since 01/01/1972 - 01/01/2107
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...