![BENSHAW RediStart EXEXMVRMX3 Series User Manual Download Page 75](http://html1.mh-extra.com/html/benshaw/redistart-exexmvrmx3-series/redistart-exexmvrmx3-series_user-manual_2735255075.webp)
Maximum Current 1
CFN 04
LCD Display
Range
100 – 800 % of FLA
(Default: 600%)
Description
The Maximum Current 1 parameter is set as a percentage of the Motor FLA (QST 01) parameter setting and
performs two functions. It sets the current level for the end of the ramp profile. It also sets the maximum
current that is allowed to reach the motor after the ramp is completed.
If the ramp time expires before the motor has reached full speed, the starter holds the current at the maximum
current level until either the UTS timer expires, the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower
maximum current.
See Also
Up To Speed Time (QST 09) on page 62.
Start Mode (CFN 01) on page 63.
Ramp Time 1 (QST 08 / CFN 02) on page 64.
Initial Current 1 (QST 06 / CFN 03) on page 64.
Kick Level 1 (CFN 11) on page 68.
Kick Time 1 (CFN 12) on page 69.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramps and Times on page 123.
Ramp Time 2
CFN 05
LCD Display
Range
0 – 300 seconds
(Default: 15 seconds)
Description
The Ramp Time 2 parameter sets the time it takes for the starter to allow the current to go from the initial
current to the maximum current when the second ramp is active. Refer to the Ramp Time 1 (QST 08 / CFN
02) for description of operation.
See Also
Ramp Time 1 (QST 08 / CFN 02) on page 64.
Digital Input Configuration (I/O 01-08) on page 90.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramp and Times on page 123.
Theory of Operation section 7.3.6, Dual Acceleration Ramp Control on page 128.
Initial Current 2
CFN 06
LCD Display
Range
50 – 600 % of FLA
(Default: 100%)
Description
The Initial Current 2 parameter is set as a percentage of the Motor FLA (QST 01) parameter setting when the
second ramp is active. Refer to the Initial Current 1 (CFN 03) parameter for description of operation.
See Also
Initial Current 1 (CFN 03) on page 64.
Digital Input Configuration (I/O 01-08) on page 90.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramps and Times on page 123.
Theory of Operation section 7.3.6, Dual Acceleration Ramp Control on page 128.
65
6 - PARAMETER DESCRIPTION
CFN: Ramp Time 2
05
15 sec
CFN: Init Cur 2
06
100 %
CFN: Max Cur 1
04
600 %
Summary of Contents for RediStart EXEXMVRMX3 Series
Page 2: ......
Page 10: ......
Page 11: ...1 Introduction 1...
Page 17: ...2 Technical Specifications 7...
Page 27: ...3 Installation 17...
Page 48: ......
Page 49: ...4 Keypad Operation 39...
Page 59: ...5 Parameter Groups 49...
Page 67: ...6 Parameter Description 57...
Page 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Page 123: ...7 Theory of Operation 113...
Page 155: ...NOTES 145 7 THEORY OF OPERATION...
Page 156: ...146 7 THEORY OF OPERATION...
Page 157: ...8 Troubleshooting Maintenance 147...
Page 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Page 186: ......
Page 187: ...Appendices 177...
Page 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Page 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...