M470039-01 REV-F
Page 139
APPENDIX B: PLW – Cooling System Guidelines
1)
GPM Requirements:
AMETEK recommends installing a Water Flow Meter to Monitor GPM Flow
2)
PLW HEATSINK TEMPERATURE VS GPM CURVES
Model Type Water Temp (°C) GPM Model Type Water Temp (°C) GPM
PLW6K
10°C
2
PLW36K
10°C
12
15°C
2.5
15°C
15
20°C
3
20°C
18
PLW12K
10°C
4
PLW48K
10°C
16
15°C
5
15°C
20
20°C
6
20°C
24
PLW24K
10°C
8
PLW60K
10°C
20
15°C
10
15°C
25
20°C
12
20°C
30