126
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
BV10
RUN/STOP CMD
This object commands a drive
start. Control requires bypass
parameter 1601 value = comm.
RUN/STOP
C
BV11
FWD/REV CMD
This object commands a motor
rotation direction change.
Control requires 20.11 =
request (0) and drive configured
to receive the reference over
the fieldbus.
REV/FWD
C
BV12
RUN
PERMISSIVE
CMD
This object commands Run
Permissive. Control requires
parameter 1601 value = COMM.
ENABLE/
DISABLE
C
BV13
EXT 1/2 CMD
This object selects EXT1 or
EXT2 as the active control
source. Control requires
parameter 19.11 value = EFB
MCW bit 11 (32).
EXT2/EXT1
C
BV14
FAULT RESET
This object resets a faulted
drive. The command is
rising-edge triggered.
RESET/NO
C
BV15
MBOX READ
This object reads a parameter
(defined by AV25 MBOX
PARAM) and returns it in AV26
MBOX DATA.
READ/RESET
W
BV16
MBOX WRITE
This object writes the data value
specified by AV26, MBOX
DATA, to a parameter (defined
by AV25, MBOX PARAM).
WRITE/RESET
W
BV17
LOCK PANEL
This object locks the panel and
prevents parameter changes.
The corresponding drive
parameter is 96.02.
LOCK/UNLOCK W
BV18
CTL OVERRIDE
CMD
This object commands the drive
into BACnet Control Override.
In this mode, BACnet takes
drive control from the normal
source. However, the control
panel’s HAND mode has priority
over BACnet Control Override.
ON/OFF
C
BV19
CTL OVERRIDE
ACT
This object indicates whether
the drive is in BACnet Control
Override. (See BV18.)
ON/OFF
R
BV20
START
INTERLOCK 1
This object commands start
interlock1. Control requires
bypass parameter 1603 value =
COMM.
ENABLE/
DISABLE
C
BV21
START
INTERLOCK 2
This object commands start
interlock1. Control requires
bypass parameter 1604 value =
COMM.
ENABLE/
DISABLE
C
BV24
STARTED MON
This object indicates the drive’s
started status.
START/NO
START
R
Instance
ID
Object Name
Description
Active/Inactive
Text
Present Value
Access Type
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......