![background image](http://html.mh-extra.com/html/abb/ach580-series/ach580-series_user-manual_2512133.webp)
124
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
Binary output object instance summary – Drive
The following table summarizes the Binary Output Objects supported:
BI4
RO 5 ACT
This object indicates the status of Relay
Output 5 (requires CMOD-01 or
CHD-01 option).
ON/OFF
R
BI5
DO 1 ACT
This object indicates the status of Relay
Output 6 (requires CMOD-01 option).
ON/OFF
R
BI6
DI 1 ACT
This object indicates the status of Digital
Input 1.
ON/OFF
R
BI7
DI 2 ACT
This object indicates the status of Digital
Input 2.
ON/OFF
R
BI8
DI 3 ACT
This object indicates the status of Digital
Input 3.
ON/OFF
R
BI9
DI 4 ACT
This object indicates the status of Digital
Input 4.
ON/OFF
R
BI10
DI 5 ACT
This object indicates the status of Digital
Input 5.
ON/OFF
R
BI11
DI 6 ACT
This object indicates the status of Digital
Input 6.
ON/OFF
R
Instance
ID
Object Name
Description
Active/
Inactive Text
Present Value
Access Type
BO0
RO1 CMD
This object controls the output stateof
Relay 1. This control requires that drive
parameter 10.24 value = 62 (RO/DIO
CONTROL WORD).
ON/OFF
C
BO1
RO2 CMD
This object controls the output state of
Relay 1. This control requires that drive
parameter 10.27 value = 62 (RO/DIO
control word).
ON/OFF
C
BO2
RO3 CMD
This object controls the output state of
Relay 1. This control requires that drive
parameter 10.30 value = 62 (RO/DIO
control word).
ON/OFF
C
BO3
RO4 CMD
This object controls the output state of
Relay 1. This control requires that drive
parameter 15.07 value = 62 (RO/DIO
control word). Also requires CMOD-01
option.
ON/OFF
C
Instance
ID
Object
Name
Description
Active/
Inactive Text
Present Value
Access Type
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......