ACH580 E-Clipse bypass and packaged drive user manual
119
Embedded fieldbus
Feedback from the drive
Pre-defined feedback
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data.
Mailbox read/write
The E-Clipse bypass provides a “Mailbox” function to access parameters that have
not been pre-defined by the protocol. Using mailbox, any drive parameter can be
identified and read. Mailbox can also be used to adjust parameter settings by writing
a value to any drive or bypass parameter identified. The following table describes the
use of this function.
Drive Parameter
BACnet
01.01
Motor Speed Used
AV0
01.06
Output Frequency
AV1
01.07
Motor Current
AV4
01.10
Motor Torque
AV5
01.14
Output Power
AV6
01.11
DC Voltage
AV2
01.13
Output Voltage
AV3
01.57
Inverter KWH Counter (resettable)
AV8
10.02
DI Delayed Status
BI6
10.21
RO Status
BI0
58.19
EFB Status Word – bit 0 (STOP)
BV0
58.19
EFB Status Word – bit 2 (REV)
BV1
Name
Description
BACnet Access Point
Drive node
objects
Bypass node
objects
Mailbox Parameter
Enter the number of the drive group and
parameter number using the format:
(group #) * 256 + parameter #.
Example: drive parameter 28.01 is entered as
(28 * 256) + 1 = 7169
AV25
AV13
Mailbox Data
Contains the parameter value after a read, or
enter the desired parameter value for a write.
AV26
AV14
Mailbox Read
A binary value triggers a read – the value of the
“Mailbox Parameter” appears in “Mailbox data”.
BV15
BV21
Mailbox Write
A binary value triggers a write – the drive value
for the “Mailbox Parameter” changes to the
value in “Mailbox data”.
BV16
BV22
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......